English-
10
Terminal
Symbol
Terminal Function
Factory Settings (NPN mode)
ON: Connect to DCM
MO1
Multi-function Output 1
(Photocoupler)
Maximum 48VDC, 50mA
Refer to Pr.03.01 for programming
MO1-DCM
Mo1
MCM
Max: 48Vdc
50mA
internal circuit
MCM Multi-function
output
common Common for Multi-function Outputs
+10V
Potentiometer power supply
+10VDC 3mA
AVI
Analog voltage Input
ACM
AVI
+10V
internal circuit
AVI circuit
Impedance: 47k
Ω
Resolution: 10
bits
Range:
0 ~ 10VDC =
0 ~ Max. Output Frequency
(Pr.01.00)
Selection: Pr.02.00,
Pr.02.09,
Pr.10.00
Set-up:
Pr.04.11 ~ Pr.04.14
ACM
Analog control signal
(common)
Common for AVI, ACI, AFM
ACI
Analog current Input
ACM
ACI
internal circuit
ACI circuit
Impedance: 250
Ω
Resolution: 10
bits
Range:
4 ~ 20mA =
0 ~ Max. Output Frequency
(Pr.01.00)
Selection: Pr.02.00,
Pr.02.09,
Pr.10.00
Set-up:
Pr.04.15 ~ Pr.04.18, 04.19~04.23
AFM
Analog output meter
AFM
ACM
0~10V
Max. 2mA
potentiometer
ACM circuit
internal circuit
0 to 10V, 2mA
Impedance: 20k
Ω
Output current
2mA max
Resolution: 8
bits
Range:
0 ~ 10VDC
Function:
Pr.03.03 to Pr.03.04
NOTE: Control signal wiring size: 18 AWG (0.75 mm
2
) with shielded wire.
Summary of Parameter Settings
a
: The parameter can be set during operation.
Pr.
Explanation
Settings
Factory
Setting
NOTE
Group 0 User Parameters
00.00
Identity Code of the
AC motor drive
Read-only ##