ACC-72EX User Manual
Software setup
77
Click Device Assignment under the Driver folder in the Navigation Area. Assign the netX Driver to the
detected COMX module by checking the checkmark box next to the detected device, and click Apply.
Note
When used with Turbo PMAC, the reset line is released too fast for
some Hilscher COMX modules, which puts them in a boot mode.
This can prevent the device from being detected by Sycon.NET
software. Make sure the device receives a system-wide reset using the
PMAC suggested M-Variables ulSystemCommandCOS and
HSF_RESET registers as shown here.
SCtrl_ulSystemCommandCOS=$55AA55AA
HCSC_HSF_RESET=1
Note that ACC-72EX Setup Assistant software automatically resets
the cards if it cannot detect the identification cookie.
The rest of the steps are protocol/module dependent, and it is strongly recommended to follow the
directions for these modules in Hilscher documentation available through their website. The current
example will be continued with specifics to EtherNet/IP Scanner/Adapter setup.