background image

BECT832-SSO  Screwdriver Controller

Operation Manual

DELTA REGIS

Tools Inc.

www.deltaregis.com

 

SW 5 - Evaluate Rundown Time

 

When SW 5 is moved to the ON position, the controller enters a rundown evaluation mode, which can 

assist in determining proper time window settings to program for the application. The operator will be allowed 

to run multiple rundown cycles (as many as desired) and the display will show the actual cycle time for each 

rundown. Certain program parameters must be entered after SW 5 is turned on, before the actual testing can 

start. Please keep in mind that the fastener rundown time will change if any adjustments are made to running 

speed (Hi/Lo), slow start speed, or slow start time. It is important that these adjustments are finalized before 

using this rundown evaluation procedure.

The test sequence is as follows: 

(Note: The parameter setup portion of this test follows the standard 

programming flow chart outlined earlier in the manual.)

1.  Move DIP SW5 to the ON position.

2. 

The display flashes a value (eg. U1) - this value is the sequence number (SL) that the controller will use for 

setup of the rundown parameters. If you wish to use a different sequence number, use the UP/DN arrow 

keys to change.

3.  Press SELECT. ‘SC’ will show in the display, followed by a value. Adjust the value to the desired ‘batch 

count setting’ for your application.

4.  Press SELECT. ‘Rt’ will show in the display, followed by a value. Adjust the value to the desired ‘end of 

batch reset time’ for your application.

5.  Press SELECT. ‘RC’ will show in the display, followed by a value. Adjust the value to the desired ‘slow start 

time’ for your application.

6.  Press SELECT. ‘SP’ will show in the display, followed by a value. Select a value for the desired slow start 

speed (L0-L9). Refer to pg 10 for further details on speed settings.

7.  Press SELECT. The display shows ‘0.0’. The tool is now ready to run tests. Use the screwdriver to 

rundown the fastener on the application. The display will count up time in 0.1 second increments until the 

cycle completes. Once complete, the cycle time will show in the display. Repeat the rundown as many 

times as desired.

8.  Move SW5 to the OFF position. The controller will program the last recorded rundown time as the 

sequence’s Max. Acceptable Rundown Time (Ht) value. The controller returns to normal operation mode 

and displays the batch count value.

9.  Enter the Programming Mode (press and hold SELECT for 5 sec) to review/verify the settings and make 

any final adjustments to the time window values. 

Please refer to the programming flow chart for further 

details on settings and values.

SW 6 - Multiple Rundown Sequences

 

With SW6 in the OFF position, the controller will run only the current program sequence to complete 

the batch - it will not step to the next programmed sequence.

If you have multiple sequences programmed which you wish to run sequentially (

see Sequence Number 

(SL) on the programming page

), setting SW6 to ON will cause the controller to step through the programmed 

sequences in order until they have all been completed. A batch complete signal will be output once all 

sequences have completed, and the controller will loop back to the start of sequence SL=U1 to start the next 

batch. Note - if the controller encounters a sequence with a screw batch count (SC) set as zero, the controller 

identifies this as the end of the sequences and will loop back to the beginning to start a new batch.

SW 7 - Decrement Count on Reverse

 

Following an OK rundown, if the operator switches the tool into REV and activates the trigger, the 

count will decrement. With SW 7 OFF, the count will decrement by one screw. With SW 7 ON, the count will 

decrement for each trigger activation in reverse (until the start count value has been reached).

Page 13

Summary of Contents for BECT832-SSO

Page 1: ...ively with the following Delta Regis Brushless Electric Screwdrivers CESL810 812 CESL823 F P PF CESL824 F P PF CESL827 P Do not attempt to use this controller with any other tools If you have any questions or concerns please contact us at Delta Regis Tools Inc 6945 LTC Pkwy Port St Lucie FL 34946 USA Ph 1 772 465 4302 Fx 1 772 465 4368 E mail sales deltaregis com Website www deltaregis com Doc BEC...

Page 2: ...maximum current rating an internal fuse will disrupt power Should the controller stop functioning or exhibit abnormal or intermittent operation please discontinue use immediately and send the controller to an authorized service centre for troubleshooting and repair 11 Excessive duty cycle will cause the tool and or controller to overheat If this occurs discontinue use until cooled down and reduce ...

Page 3: ...unt Setting Range rundowns batch 1 99 Time Window Settings Minimum acceptable rundown time 0 00 9 90 seconds 0 01 sec increments Maximum acceptable rundown time 0 0 9 9 seconds 0 1 sec increments Audible Alarm Settings selectable On sounds when Good No Good Batch Complete OF sounds when No Good FF sounds when Batch complete No Good EF sounds when Good Batch Complete Input Connections Remote Start ...

Page 4: ...E RECEPTACLE AND MAIN POWER ON OFF SWITCH SCREWDRIVER CABLE CONNECTOR SCREWDRIVER HI LO SPEED SELECTOR INPUT OUTPUT CONNECTION TERMINAL BLOCK DIP SWITCH FOR SELECTING OPTIONAL FUNCTIONS Page 4 Front Face of Controller Rear Panel of Controller KEYPAD AND INDICATORS FOR PROGRAMMING AND STATUS MONITORING PROGRAM FUNCTION KEY LOCK ...

Page 5: ...ctor switch from HI to LO will toggle between the two available speeds voltages Keypad and Programming Basics Page 5 ON CLEAR KEY Pressing and holding the ON button for 5 seconds will cause the display to go blank In this mode the screwdriver will function at HI LO speed but there will be no other functionality counting slow start etc Pressing ON from this mode will restore the display and added f...

Page 6: ...verse the batch count value will decrement by a count of one based on the assumption that the operator is removing the last installed fastener The batch count can be reset to begin a new batch by pressing the ON CLEAR key END OF BATCH RESET TIME Rt When a rundown batch is completed the controller provides a visual indication count 00 and audible indication depending on audible settings that the ba...

Page 7: ... a value lower than High Time Ht during programming or an error Er will occur Ht value must be Lt SEQUENCE LIST 5 available sequences PressandholdSELECT forabout5seconds until SL displays Releaseto view programmedvalue SEQUENCE U1 U5 select to edit Adjustvalue UP DOWN Pressuntil SC displays Releaseto viewvalue Adjustvalue UP DOWN SCREW BATCH COUNT of screws per batch MIN 00 screws MAX 99 screws Pr...

Page 8: ... is only available if Slow Start Time RC is set to 0 0 slow start off The re hit function can t be used in conjunction with slow start nS Disable Screwdriver on NG If nS is set to y yes the screwdriver will be disabled after a no good NG rundown The operator must confirm by pressing the SELECT key or an external confirm signal must be input through the I O applies to forward cw rotation only rt Au...

Page 9: ...h tt until the operator runs the driver and completes the batch Only one of the two optional alarms can be selected for use Page 9 MAX STANDBYTIME BETWEEN RUNDOWNS Time seconds Range 00 99 Pressuntil dt or tt displays Releaseto viewvalue Adjustvalue UP DOWN MAX TOTAL BATCH TIMEWARNING Time minutes Range 00 99 Adjustvalue UP DOWN n no y yes Togglevalue GATE SWITCH INPUT PREFERRED LOGIC Hi Lo Toggle...

Page 10: ...further details on entering parameters Audible Alarm Settings OK and NG Lights Along with the two digit count display the controller also provides visual and audible indication of rundown OK rundown NG and batch complete The OK green and NG red lamps indicate whether the rundown was GOOD or NO GOOD If the rundown is within the set parameters the OK lamp will light up at the end of the rundown cycl...

Page 11: ...external confirmation that the process can continue see DIP SW3 description OFF ON OFF ON OFF ON OFF ON Page 11 Output Terminals OUTPUT TERMINALS 2 thru 7 Connection pairs 2 3 4 5 and 6 7 are dry relay contact outputs AC DC 40V 250mA max INPUT TERMINALS 8 thru 13 COM 14 Connect an external switch between COM terminal 14 and the input terminal 8 13 Use a separate switch contact for each required in...

Page 12: ... the previous batch Placing SW3 in the ON position will require the operator to press the SELECT button or require an external CONFIRM input at the end of each batch before the controller will reset to run a new batch Upon batch completion the display will flash C3 and the screwdriver will be disabled until the SELECT button is pressed or a CONFIRM signal is input SW 4 Multiple External Switch Inp...

Page 13: ...urther details on speed settings 7 Press SELECT The display shows 0 0 The tool is now ready to run tests Use the screwdriver to rundown the fastener on the application The display will count up time in 0 1 second increments until the cycle completes Once complete the cycle time will show in the display Repeat the rundown as many times as desired 8 Move SW5 to the OFF position The controller will p...

Page 14: ...utch E7 FWD REV Switch Error Controller detected a change in the position of the FWD REV switch while the tool was running FWD REV Button was moved by the operator during rundown switch PCB improperly positioned in tool housing or magnetic switching element has failed E8 Brake Error Controller detected an abnormal brake clutch signal before the tool was started clutch is stuck at the top of the cl...

Page 15: ...t max time value The BECT832 SSO Controller is not user serviceable Any repairs must be performed by a Delta Regis authorized service center Please consult Delta Regis Tools for further information and the location of the nearest authorized service center Repairs to brushless DC screwdrivers must be performed by trained personnel knowledgeable and qualified in the repair of DC electric screwdriver...

Reviews: