Configuring Output Devices
1. Command the Learn Mode BV object to On. The Link Status CSV object changes to
"Pairing."
2. On the EnOcean output device, generate a learn packet from the device using the method
specified by the manufacturer. When pairing is complete, the Device Address CSV object
shows the device’s ID and the Link Status CSV object changes to "Online."
3. Once pairing is complete, command the Learn Mode BV object to Off.
4. Confirm that the feedback value matches the actual output value or state.
Configuring Radiator Valve Controllers
A radiator valve controller is an actuator for a heating radiator application that uses the A5-20-
04 EEP profile (FIL1227).
The mapping file should contain the following objects:
Name
Reference (O3 Hub)
Reference (CON-ENOC)
Temperature
AV3sDD001 (e.g., AV3201001)
AVpDD001 (e.g., AV101001)
4BS Variation 3
BV3sDD981
BVpDD981
RPS Force Send
BV3sDD982
BVpDD982
Total Send Error
AV3sDD983
AVpDD983
Total Send
AV3sDD984
AVpDD984
4BS Send
BV3sDD985
BVpDD985
4BS Learn Out
BV3sDD986
BVpDD986
Learn Out Func
CSV3sDD987
CSVpDD987
Learn Out Type
CSV3sDD988
CSVpDD988
Three Click Learn Out
BV3sDD989
BVpDD989
OFF Value
BV3sDD989
AVpDD990
ON Value
AV3sDD990
AVpDD991
One Click Learn Out
BV3sDD992
BVpDD992
Device Type
AV3sDD993
AVpDD993
©