Monitoring Network Communication
Name
Reference (O3 Hub)
Reference (CON-ENOC)
Reliability Timer
AV3sDD997
AVpDD997
s = hub rotary switch address (2–9) p = controller NET port (1–3) DD = EnOcean device number (01–32)
The Reliability Timer object displays a value in seconds (although the unit displays as %). When
a new packet is received, the timer resets and begins another count down cycle. If a new packet
is not received from the paired EnOcean device before the timer expires, the Link Status CSV
object changes to Offline. To disable the Reliability Timer for a device, manually set the
Reliability Timer object value to 0.
Monitoring Communication Statistics
Incoming and outgoing communications statistics provide a way to verify that EnOcean data is
being transferred without an excessive number of errors.
Name
Reference (O3 Hub)
Reference (CON-ENOC)
Total Send Error
AV3sDD983
AVpDD983
Total Send
AV3sDD984
AVpDD984
Total Receive Error
AV3sDD994
AVpDD994
Total Receive
AV3sDD995
AVpDD995
s = hub rotary switch address (2–9) p = controller NET port (1–3) DD = EnOcean device number (01–32)
The ratio of error packets to total packets received should be less than 5 percent.
The Total Receive object holds the count for total packets received with no errors. The Total
Receive Error object holds the count for total packets received with errors.
The Total Send object holds the count for total packets sent with no errors. This number is
reported by the EnOcean transceiver and does not necessarily mean that the packets were
received at their destination. The Total Send Error object holds the count for total packets sent
with errors. The Total Send count does not include packets that cause the Total Send Error
count to be incremented.
You can create an AV object (AV30
s059) to monitor the total number of packets received by a
particular O3 Hub. However, this will also count packets received with errors, so it is not a good
indicator of the total number of successful packets.
©