Configuring Output Devices
24
O3-DIN EnOcean Application Guide
Edition 1.0
Name
Reference (O3 Hub)
Reference (CON-ENOC)
Total Receive Error
AV3sDD994
AVpDD994
Total Receive
AV3sDD995
AVpDD995
Link Status
CSV3sDD996
CSVpDD996
Reliability Timer
AV3sDD997
AVpDD997
Learn Mode
BV3sDD998
BVpDD998
Device Address
CSV3sDD999
CSVpDD999
s = hub rotary switch address (2–9) p = controller NET port (1–3) DD = EnOcean device number (01–32)
The following procedure assumes that you have already completed steps 1 to 4 in Main Steps
for Configuring Output Devices and that you've associated the A5-20-04 profile with the device
SV object.
To configure a radiator valve controller:
1. Create the mapping and configuration objects needed for your application.
2. Command the 4BS Variation 3 BV object to On.
3. Ensure that all Learn Out BV objects are Off.
4. Set the value of the Learn Out Func CSV object to 20.
5. Set the value of the Learn Out Type CSV object to 04.
6. Command the Learn Mode BV object to On.
7. Put the radiator valve controller into learn mode. For specific instructions, consult the
manufacturer's documentation.
8. Command the 4BS Learn Out BV object to On. The Device Address CSV object should show
the device's ID.
9. Command the 4BS Learn Out BV object and the Learn Mode BV object to Off.
10. Confirm that the radiator valve controller responds correctly when you send a command.
To control a radiator valve controller:
1. Ensure that the Learn Mode BV object is Off.
2. Set the control parameters based on the
profile.
3. Set a value for an object such as the valve position.