Working With Mapping Files
This section covers the following topics:
l
Modifying a Default Mapping File
l
Creating a Custom XML Mapping File
l
The O3-DIN EnOcean gateway supports both standard EEP profiles and custom XML files for
mapping.
The EEP profiles included in the default database (FIL1201–1227) should be used whenever
possible. Additional tested profiles may be available on
. You can also
contact
Delta's Professional Development Services
group to have a custom mapping file made.
Modifying a Default Mapping File
Occasionally, you may want to modify one of the default EEP mapping files. For example, you
may want to adjust the range and scale values.
To modify a default mapping file:
1. Open the FIL object you want to modify (e.g., FIL1215) and click
Download File
. The XML
file (A5-10-10_4BS_Telegram_Room_Operating_Panel_Temperature_and_Humidity _
Sensor_Set_Point_and_Occupancy_Control.xml) is saved to the Downloads folder.
2. Create a new FIL object (e.g., FIL115).
3. Open the new FIL object (e.g., FIL115) and click
Upload File
. Upload the XML file you
downloaded in step 1.
4. Modify the mapping values in the Translation table as needed.
l
To edit a value, double-click the value you want to edit, enter the new value, then click
Save
.
l
To add a new mapping row, click
Add
, double-click each cell and enter the desired value,
then click
Save
.
l
To copy a mapping row, select the row, then click
Copy
. The row is added to the end of
table.
l
To delete a mapping row, select the row, then click
Delete
.
If no values appear in the Translation table, the uploaded XML file may contain invalid syntax or
unsupported options.
If a FIL object associated with a Device SV object is changed or edited, a controller
reboot is required to clear data from the previous profile.
32
O3-DIN EnOcean Application Guide
Edition 1.0