- 2 -
External Wiring
PT100
PT100
CH1
CH4
1mA
DC/ DC
5V
AG
+15V
-15V
AG
AG
AG
24+
24-
FG
,
L-
L+
FG
,
L-
L+
Converter
System
Class 3 Grounding
(100 of less)
terminal of
pow er m odule
Shielded* 1
*2
*3
1mA
Shielded* 1
Grounding
[ Figure 2 ]
Note1:
Use only the wires that are packed with the temperature sensor (PT100) for analog input
and separate from other power line or any wire that may cause noise. Please use 3-wire
for PT100.
Note2:
Terminal FG is grounded for noise suppression.
Note3:
Please connect
power supply module terminal and
DVP04PT-S temperature
measurement module terminal to system earth ground.
Warning:
DO NOT connect wires to the No Connection terminals.
Electrical Specifications
DVP04PT-S
Power supply voltage 24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)
Max. rated power
consumption
2W, supplied by external power.
Operation/storage
Operation: 0°C~55°C (temp.), 50~95% (humidity), pollution degree 2
Storage: -25°C~70°C (temp.), 5~95% (humidity)
Vibration/shock
resistance
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/
IEC61131-2 & IEC 68-2-27 (TEST Ea)
Series connection to
DVP-PLC MPU
The modules are numbered from 0 to 7 automatically by their distance
from MPU. No.0 is the closest to MPU and No.7 is the furthest.
Maximum 8 modules are allowed to connect to MPU and will not
occupy any digital I/O points.
Functional Specifications
DVP04PT-S
Celsius (°C)
Fahrenheit (°F)
Analog input channel
4 channels per module
Sensors type
3- WIRE PT 100
ȍ
3850 PPM/°C (DIN 43760 JIS C1604-1989)
Current excitation
1mA
Temperature input range -200°C ~ 600°C
-328°F ~ 1112°F
Digital conversion range
K-2,000 ~ K6,000
K-3,280 ~ K11,120
Resolution
14 bits (0.1°C)