VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-33
1
2
3
4
5
60Hz or more
50Hz
10Hz
5Hz
Load
factor
(%)
Operation
Time(min)
0
20 40 60 80 100 120 140 160 180 200
06 - 08
Low Current Detection Level
Factory Setting: 00
Settings
00~100% (00 disabled)
Unit: 1
06 - 09
Low Current Detection Time
Factory Setting: 10.0
Settings
0.1~ 3600.0 Sec
Unit: 0.1
06 - 10
Low Current Detection Treatment
Factory Setting: 01
Settings
00: Warn and Ramp to stop
01: Warn and Coast to stop
02: Warn and keep operating
These parameters set the low current detection mode, time, and operation.
06 - 11
Present Fault Record
Factory Setting: 00
06 - 12
Second Most Recent Fault Record
Factory Setting: 00
06 - 13
Third Most Recent Fault Record
Factory Setting: 00
06 - 14
Fourth Recent Fault Record
Factory Setting: 00
Settings
00
No fault occurred
01
Over-current
(oc)
02
Over-voltage
(ov)
03
Overheat
(oH)
04
Overload
(oL)
05
Electronic thermal relay (oL1)
06
External
fault
(EF)
07
AC drive IGBT fault (occ)
08
CPU failure (cF3)
09
Hardware protection failure (HPF)