
5
VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-67
11 - 02
Multiple Motors Control
Factory Setting: 01
Settings
01~04
When this parameter is set to multiple motors control, multi-function terminals 03-00 to
03-07 will automatically set to suitable value. Users need to connect output terminal
correctly to circulative control as shown in following chart.
11-01
Circulative
Control
01
Time Circulation
02
Fixed Amount Circulation
11-02
motors
01 02 03 04 01 02 03 04
03-00 01
Motor 1 runs
by AC drive.
01
Motor 1 runs
by AC drive.
01
Motor 1 runs
by AC drive.
01
Motor 1 runs
by AC drive.
01
Motor 1 runs
by AC drive.
01
Motor 1 runs
by AC drive.
01
Motor 1 runs
by AC drive.
01
Motor 1 runs
by AC drive.
03-01 N/A
02
Motor 2 runs
by AC drive.
02
Motor 2 runs
by AC drive.
02
Motor 2 runs
by AC drive.
02
Motor 1 runs
by
commercial
power.
02
Motor 1 runs
by
commercial
power.
02
Motor 1 runs
by
commercial
power.
02
Motor 1 runs
by
commercial
power.
03-02 N/A
N/A
03
Motor 3 runs
by AC drive.
03
Motor 3 runs
by AC drive.
N/A 03
Motor 2 runs
by AC drive.
03
Motor 2 runs
by AC drive.
03
Motor 2 runs
by AC drive.
03-03
N/A N/A N/A 04
Motor 4 runs
by AC drive.
N/A 04
Motor 2 runs
by
commercial
power.
04
Motor 2 runs
by
commercial
power.
04
Motor 2 runs
by
commercial
power.
03-04
N/A N/A N/A N/A N/A N/A 05
Motor 3 runs
by AC drive.
05
Motor 3 runs
by AC drive.
03-05
N/A N/A N/A N/A N/A N/A 06
Motor 3 runs
by
commercial
power.
06
Motor 3 runs
by
commercial
power.
03-06
N/A N/A N/A N/A N/A N/A N/A 07
Motor 4 runs
by AC drive.
03-07
N/A N/A N/A N/A N/A N/A N/A 08
Motor 4 runs
by
commercial
power.
11 - 03
Time Circulation Time Setting
Factory Setting: 00
Settings
00~65500 Min
Unit: 1 Min
This parameter is to set running time of each motor (including acceleration time) when
multiple motors are in time circulation mode (11-01=1). If this parameter is set to 00, time
setting is disabled and run with a motor.
Summary of Contents for AC Drive VFD-F Series
Page 1: ......
Page 2: ......
Page 3: ......
Page 107: ...VFD F Series DELTA ELECTRONICS INC ALL RIGHTS RESERVED This page intentionally left blank...
Page 133: ...VFD F Series DELTA ELECTRONICS INC ALL RIGHTS RESERVED This page intentionally left blank...
Page 161: ...VFD F Series DELTA ELECTRONICS INC ALL RIGHTS RESERVED C 8 KPF CC01 Unit mm inches...