When this parameter is set to 01: when positive control, the deviation equation is deviation
= detection signal – target value. When increasing output frequency will decrease detection
value, this setting should be chose.
10 - 03
Proportional Gain (P)
Factory Setting: 1.0
Settings
0.0~10.0
Unit:
0.1
This parameter is to set proportional gain (P). This gain determines the response degree of
P controller to feedback deviation. If gain value is large, the response is fast. But if the gain
value is too great, oscillation will occur. If gain value is small, the response is slow.
10 - 04
Integral Time (I)
Factory Setting: 1.00
Settings
0.00~100.00 Sec
Unit: 0.01
This parameter is set to integral gain of I controller. When much integral time is to be set,
the gain of I controller is small and the response is slow. The control ability to external is
poor. When less integral time is to be set, the gain of I controller is large and the response is
fast. The control ability to external is fast.
If the setting of integral time is too small, output frequency and system may occur
oscillation.
If integral time is set to 0.00, I controller is closed.
10 - 05
Differential Time (D)
Factory Setting: 0.00
Settings
0.00~1.00
Sec
Unit:
0.01
This parameter is set to D controller gain. This gain determines D controller to the response
of change of deviation. Suitable differential time could decrease overshoot of P and I
controller. The oscillation will be attenuation and steady quickly. But if much differential time
is to be set, it may cause system oscillation.
Interference immunity ability is poor due to differential controller activates to change of
deviation. It’s not recommended to use, especially during interferences.
10 - 06
Upper Bound for Integral Control
Factory Setting: 100
Settings
00~200%
Unit:
1
This parameter could set the upper bound of I controller. In other words, upper bound for
integral control = (01-00) X (10-04) %
10 - 07
Primary Low Pass Filter Time
Factory Setting: 0.0
Settings
0.0~2.5
Sec
Unit:
0.1
This parameter determines primary Low Pass filter time.
Summary of Contents for AC Drive VFD-F Series
Page 1: ......
Page 2: ......
Page 3: ......
Page 107: ...VFD F Series DELTA ELECTRONICS INC ALL RIGHTS RESERVED This page intentionally left blank...
Page 133: ...VFD F Series DELTA ELECTRONICS INC ALL RIGHTS RESERVED This page intentionally left blank...
Page 161: ...VFD F Series DELTA ELECTRONICS INC ALL RIGHTS RESERVED C 8 KPF CC01 Unit mm inches...