8
VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-15
Group 8 Special Parameters (Twice the value for 460V class)
Parameters Functions
Settings
Factory
Setting
Customer
08-00 DC Brake Current Level
00~100%
00
08-01 DC Brake Time during Start-up 0.0~60.0 Sec
0.0
08-02 DC Brake Time during Stopping 0.00~60.00 Sec
0.0
08-03 Start-point for DC Brake
0.00~120.00 Hz
0.00
08-04 Momentary
Power
Loss
Operation Selection
00: Disable
01: Trace from top downward
02: Trace from bottom
upward
00
08-05 Maximum
Allowable
Power
Loss Time
0.1~5.0 Sec
2.0
08-06 Speed Search Time
0.1~5.0 Sec
0.5
08-07 Maximum
Speed
Search
Current
30~150% 110
08-08 BB speed search method
00: Trace from top downward
01: Trace from bottom
upward
00
08-09 Auto Restart Times after Fault 00~10
00
08-10 Auto Restart Time after Fault
00 to 60000 sec
600
08-11 Operation Frequency Inhibition
1 UP
0.00~120.00 Hz
0.00
08-12 Operation Frequency Inhibition
1 DOWN
0.00~120.00 Hz
0.00
08-13 Operation Frequency Inhibition
2 UP
0.00~120.00 Hz
0.00
08-14 Operation Frequency Inhibition
2 DOWN
0.00~120.00 Hz
0.00
08-15 Operation Frequency Inhibition
3 UP
0.00~120.00 Hz
0.00
08-16 Operation Frequency Inhibition
3 DOWN
0.00~120.00 Hz
0.00
08-17 Automatic
Energy-saving 00:
Energy-saving
operation
disabled
01: Energy-saving operation
enabled
00
08-18 Automatic
Voltage
Regulation
(AVR)
00: AVR function enabled
01: AVR function disabled
02: AVR function disabled for
deceleration
00
a
08-19 Software Setting of the Brake
Level
(the action level of the brake
resistor)
230V: 370~410VDC
460V: 740~820VDC
00:Disable
380.0
760.0
a
08-20 Vibration Compensation Factor 00~1000
00
Summary of Contents for AC Drive VFD-F Series
Page 1: ......
Page 2: ......
Page 3: ......
Page 107: ...VFD F Series DELTA ELECTRONICS INC ALL RIGHTS RESERVED This page intentionally left blank...
Page 133: ...VFD F Series DELTA ELECTRONICS INC ALL RIGHTS RESERVED This page intentionally left blank...
Page 161: ...VFD F Series DELTA ELECTRONICS INC ALL RIGHTS RESERVED C 8 KPF CC01 Unit mm inches...