Environmental
NOTE: When operating in the expanded
temperature range, ambient temperature warnings
may be reported on the LCD and in the System
Event Log.
≤
10% of annual operating hours
5 °C to 40 °C at 5% to 85% RH with 26 °C dew point.
NOTE: Outside the standard operating temperature
(10 °C to 35 °C), the system can operate down to 5
°C or up to 40 °C for a maximum of 10% of its
annual operating hours.
For temperatures between 35 °C and 40 °C, de-rate
maximum allowable dry bulb temperature by 1 °C per
175 m above 950 m (1 °F per 319 ft).
≤
1% of annual operating hours
–5 °C to 45 °C at 5% to 90% RH with 26 °C dew point.
NOTE: Outside the standard operating temperature
(10 °C to 35 °C), the system can operate down to –5
°C or up to 45 °C for a maximum of 1% of its annual
operating hours.
For temperatures between 40 °C and 45 °C, de-rate
maximum allowable dry bulb temperature by 1 °C per
125 m above 950 m (1 °F per 228 ft).
Expanded operating temperature restrictions
•
Do not perform a cold startup below 5 °C.
•
Allow processor performance degrade.
•
Non-redundant power supplies are not
supported.
•
Non Dell qualified peripheral cards and/or
peripheral cards are not supported.
103