R840 server installation guidelines
Minimum and maximum stack up configurations are provided in this topic.
Throughout this document, it is assumed that a 40 U rack is being used. If you plan to use a custom rack, or only part of
a rack, it is highly recommended that a complete analysis is performed in order to ensure that there is enough power
supplied to the nodes. In addition, it is essential that a custom rack has sufficient air flow and heat distribution among
nodes. Therefore, for custom rack configurations, perform an air flow analysis and ensure that there is enough spacing
between nodes.
Ensure that there is at least one redundant power zone available for power connections.
To ensure proper performance and avoid throttling, the R840 server requires the appropriate inlet temperature. Review
this requirement and maintain correct inlet temperature. For more information, see environmental specifications in the
Hardware Replacement and Services Guide
.
When systems are installed into an empty rack, always begin component installation at
the bottom of the cabinet and work upward. Install components at the lowest available
space for that component type.
If you are installing the minimum configuration, the stack up will be as follows:
Table 20 Stack up for a minimum configuration
Component Function
Description
Quantity
Cabinet U Space
Data Server
R840 Server
3
2 - 7
Management Server
Management Server
1
20
Management Switch
Customer provided 1 GbE
switch
1
21
Data Switch
Customer provided 10 GbE
switch
2
23 - 24
If you are installing the maximum configuration, the stack up will be as follows:
Table 21 Stack up for a maximum configuration
Component Function
Description
Quantity
Cabinet U Space
Data Server
R840 Server
13 - 15
3 - 19 and 25 - 39
Management Server
Management Server
1
20
Management Switch
Customer provided 1 GbE switch
1
21
Data Switch
Customer provided 10 GbE switch 2
23 - 24
The following illustration represents the maximum R840 configuration.
R840 Equipment Installation
82
Dell EMC VxFlex Ready Node Server Installation Guide
Summary of Contents for EMC VxFlex Ready Node
Page 1: ...Dell EMC VxFlex Ready Node Server Installation Guide Rev 01 October 2019 ...
Page 6: ...Figures 6 Dell EMC VxFlex Ready Node Server Installation Guide ...
Page 8: ...Tables 8 Dell EMC VxFlex Ready Node Server Installation Guide ...
Page 16: ...Before You Begin 16 Dell EMC VxFlex Ready Node Server Installation Guide ...
Page 18: ...R640 Procedures 18 Dell EMC VxFlex Ready Node Server Installation Guide ...
Page 56: ...R740XD Procedures 56 Dell EMC VxFlex Ready Node Server Installation Guide ...
Page 80: ...R840 Procedures 80 Dell EMC VxFlex Ready Node Server Installation Guide ...