Site requirements
This table lists the DS60 site requirements. See
on page 100
for hardware specifications information.
Table 3 Site requirements
Requirement
DS60 Expansion Shelf
Vertical space in standard 19", 4-post rack
5U including a 1U Cable Managements Tray.
Do not use a two-post rack. See the slide rail
and installation documentation in the
packaging for installing in a rack.
Air conditioning
Air conditioning that can cope with the
maximum BTU/hr thermal rating.
Temperature controls
Adequate temperature control with a gradient
(change) not to exceed 30° C in an hour.
Front bezel clearance
1.56 inches (4.0 cm) of unobstructed
clearance.
Back panel clearance
5 inches (12.7 cm) of unobstructed clearance.
Airflow
In a closed or multi-unit rack, ensure that the
unit has adequate airflow. If the equipment is
mounted in an enclosed (as opposed to a
four-post open rack), the front and rear doors
should have 65% minimum open area for
airflow. Whether in an open or enclosed rack,
use filler panels to prevent hot air re-
circulation. The rack design and installation
should take into consideration the maximum
ambient operating temperature of the
equipment, which is 35° C.
Power/grounding
The Power distribution within the rack should
provide a safe electrical earth connection.
Voltage should be 200-240 VAC; 50 or 60 Hz.
Plug four power cords - two from each power
supply into separate branch circuit supplies
for redundancy—one set of cords from one
power supply goes to one branch and the
second set of cords from the other power
supply goes to a different branch. Each
receptacle must be capable of safely
supplying 0.94 amps from each power socket
or 1.87 amps from each socket in case of a
redundant circuit.
DS60 Shelf Installation Overview
10
Data Domain DS60 Expansion Shelf
Hardware Guide
Summary of Contents for Data Domain DS60
Page 1: ...Dell EMC Data Domain DS60 Expansion Shelf Hardware Guide 302 002 100 REV 05 ...
Page 4: ...Hardware specifications 100 CONTENTS 4 Data Domain DS60 Expansion Shelf Hardware Guide ...
Page 8: ...Revision history 8 Data Domain DS60 Expansion Shelf Hardware Guide ...
Page 43: ...Figure 19 DD6300 Installing the Shelves DD6300 DD6800 and DD9300 cabling 43 ...
Page 80: ...Installing the Shelves 80 Data Domain DS60 Expansion Shelf Hardware Guide ...
Page 98: ...Post Installation Tasks 98 Data Domain DS60 Expansion Shelf Hardware Guide ...