Sequence components including positive, negative and neutral components are calculated. Sequence sub-menu is divided into four
groups which are Per-Unit, Primary, Secondary and Phase Angle. Each group has calculation for positive, negative and neutral
sequence components.
Figure 3.47
Harmonics view
Harmonics menu displays voltage harmonics from fundamental component up to 31th harmonic. It is possible to select whether
each component is displayed as Absolute- or Percentage and as primary or secondary amps or per unit values.
PHASORS
Figure 3.48
Phasors sub-menu
Measurement → Phasors
have vector displays for voltages. Also calculated components have own vector displays. Vectors can be
seen in own display and additionally per unit values of measured or calculated components along with secondary and primary
amplitudes are shown. Phasors are handy when it comes to solving incorrect wiring issues.
OPERATOR'S MANUAL 4189341220A UK