Figure 3.29
IED Binary Inputs menu.
All settings related to binary inputs can be found under the Binary Inputs menu. Binary inputs Settings menu includes polarity
selection for the input (normal open or normal closed), activation (16…200 V
AC/DC
, step 0.1V) and release (10…200 V
AC/DC
, step
0.1V) threshold voltage for each available input and activation delay (0…1800 s, step 1ms). Binary input statuses can be check from
corresponding menu.
Digital input activation and release threshold follows the measured peak value. Activation time of input is between 5-10 milliseconds.
Activation delay is configurable. Release time with DC is between 5-10 milliseconds. Release time with AC is less than 25
milliseconds.
Figure 3.30
Binary Outputs menu.
Polarity of binary outputs is configured between normal open (NO) and normal closed (NC) in Binary Outputs menu. As default
polarity is normal open. Operation delay of output contact is around 5 milliseconds.
OPERATOR'S MANUAL 4189341220A UK
Page 34 of 51