Page 8 of 35 Tlf. (+45) 9614 9614
·
Fax:(+45) 9752 4720
·
E-mail: [email protected]
2.6.1
Generator no. (only important with Option E)
DISPLAY Factory
set
Commis-
sioning
value
DESCRIPTION
Generator no.
01
01
Generator no. 1-8. Selection of
generator no. if more generators are
to be controlled by the power mana-
gement option E.
2.6.2 Generator
frequency
DISPLAY Factory
set
Commis-
sioning
value
DESCRIPTION
Generator freq.
f set. = 50.0 Hz
50.0
Hz
Generator frequency setpoint in
island or idle operation 48...62Hz.
2.6.3 Nominal
frequency
DISPLAY Factory
set
Commis-
sioning
value
DESCRIPTION
Nominal freq.
Generator
50.0Hz
50.0
Hz
Generator nominal frequency,
parallel running operation 48...62
Hz.
2.6.4 Generator
voltage
DISPLAY Factory
set
Commis-
sioning
value
DESCRIPTION
Generator volt.
U set. = 400 V
400V
Generator nominal voltage in island
or idle operation 350...440 V.
Volt.transformer
Prim. 10.0kV
10.0
kV
0.5...70 kV. Setting of voltage trans-
former primary value (voltage
transformer version only)
Volt.transformer
Sec. 100V
100V
100/110V. Setting of voltage trans-
former secondary value (voltage
transformer version only)