Programming manual MPC-1
4189340103E
4.4 Temperature
inputs
DISPLAY Factory
set
Commis-
sioning
value
DESCRIPTION
Analog input 5
ON
ON
ON/OFF. Selection of temperature 1 input
ON/
OFF. PTC type 0...15 k .
Name and unit
Gen PTC
000%
Fixed value.
Value at
0 % 0000
0000
Zeropoint
setpoint
Value at
100% 0060
0060
Fullscale
setpoint
Limit warning
Value = 1000
1000
0...9994. Limit for warning
Limit shutdown
Value = 1002
1002
0...9999 Limit for shutdown
Delay = 001s
001s
0...999s. Delay for both warning and
shutdown.
Monitoring:
High limit mon.
High
high limit mon./low limit mon. Selection of
high or low limit monitoring.
Temperature 6
Pt100 ON
***name****
Pt 100 1 000oC
Limit warning
= 092oC
0...255oC.
Limit shutdown
= 102oC
0...255oC.
Delay
= 001s
001s
0...999s. Delay for both warning and
shutdown.
Monitoring:
High limit mon.
High
high limit mon./low limit mon. Selection of
high or low limit monitoring.