Page 28 of 35 Tlf. (+45) 9614 9614
·
Fax:(+45) 9752 4720
·
E-mail: [email protected]
DISPLAY Factory
set
Commis-
sioning
value
DESCRIPTION
Temperature 7
Pt100 ON
***name****
Pt 100 2 000oC
Limit warning
= 092oC
0...255oC.
Limit shutdown
= 102oC
0...255oC.
Delay
= 001s
001s
0...999s. Delay for both warning and shut-
down.
Monitoring:
High limit mon.
High
high limit mon./low limit mon. Selection of
high or low limit monitoring.
4.5 Analog output manager (not available if Option E is chosen)
DISPLAY Factory
set
Commis-
sioning
value
DESCRIPTION
Analog out
X1X2
Parameter =
01
01
Parameter codes: see below
Analog out
X1X2
0% = 0000
0...9994. Value equal to 0/4mA output.
Analog out
X1X2
100% =
0000
0...9994. Value equal to 20mA output (NO-
TE: For frequency output, key in value equ-
al to f x 100. The output cannot handle de-
cimals).
Analog out
X4X5
Parameter =
01
Analog out
X4X5
0% = 0000
0...9994. Value equal to 0/4mA output.