Programming manual MPC-1
4189340103E
Analog out
X4X5
100% =
0000
0...9994. Value equal to 20mA output (NO-
TE: For frequency output, key in value equ-
al to f x 100. The output cannot handle de-
cimals).
Parameters: See next page.
The following parameters are available:
Parameter
no.
Function Description
00 No
output
01
Generator power
0% = Lowest power (kW). Can be
negative.
100% = Highest power (kW)
02
Generator cos
(-070...+070)/100
0% = Lowest factor, e.g. –010 equals -
0.1
100% Highest factor, e.g. 010 equals
+0.1
03 Generator
frequency
(Hz*100)
0% = Lowest value, e.g. 0000 equals
00.00 Hz
100% = Highest value, e.g. 7000 equals
70.00 Hz
04 Generator
reactive
power
0% = Lowest value (kvar). Can be
negative
100% = Highest value.
05
Available power for
parallel running
generators
0% = Lowest value (kW). Can be
negative
100% = Highest value.
06
Total power for parallel
running generators
0% = Lowest value (kW). Can be
negative
100% = Highest value.
07
Temperature T1 (oC)
term. 108-110
0% = Lowest value, e.g. 0000 equals
000 oC.
100% = Highest value, e.g. 0255 equals
255 oC
08
Temperature T2 (oC)
term. 111-113
0% = Lowest value, e.g. 0000 equals
000 oC.
100% = Highest value, e.g. 0255 equals
255 oC
09
Temperature T1 (oF)
term. 108-110
0% = Lowest value, e.g. 0000 equals
000 oF.
100% = Highest value, e.g. 0255 equals
255 oF
10
Temperature T2 (oF)
term. 108-110
0% = Lowest value, e.g. 0000 equals
000 oC.
100% = Highest value, e.g. 0255 equals
255 oF