ID selector
CIO 308
DEIF
LED1
LED2
S1
Firmware
8 Multi Inputs
LED1:
Red – Device failure
Green – Status output
LED2:
Red – Comm. failure
Green – Comm. OK
S1:
CANbus End resistor
8
9
10
11
12
13
14
15
16
17
18
19
B
C
I
8
A
B
C
I
11
A
B
C
I
14
A
B
C
I
17
A
B
C
I
20
A
B
C
I
23
A
B
C
I
26
A
B
C
I
29
20
21
22
23
24
25
26
27
28
29
30
31
12/24 V DC
-
+
240 Ω
Optional
4.3.4 Change text in the display
In the "Translations" section in the utility software, it is possible to change the text shown in the display. This
can be used to translate the text into another language and to change the text to something more informative
regarding what is measured. For AGC-4 and AGC PM, it is also possible to change the unit to the measure-
ment.
There are numerous languages, and the language is set in parameter 6080.
AGC-4 and AGC PM
For the input where the text should be customised, the scaling has to be set to "No unit 1/100", "No unit 1/10"
or "No unit 1/1". In the translations section, there are 3 texts to each input, where the text with 2 decimals
relates to "No unit 1/100" and so forth. As the picture below illustrates, it is also possible to configure the "CIO
- X.XX N.A." if needed.
As example, "CIO-1.17 ###.##" would relate to CIO 308 module no. 1 input 17 with scaling "No unit 1/100"
and could be changed into "Fuel tank ###.## L". The hash symbol (#) represents the digits from the measure-
ment.
CIO 308 installation and commissioning
guide 4189341078 UK
I/O setup
DEIF A/S