6.9.

 

CONVERSION TO THE OTHER GAS 

 

Adjustment  and  conversion  to  the  other  gas  can  be 
performed  only  by  the  Authorized  Service  of  the 
manufacturer. 

The rating plate with heater data for the currently used gas 
should be always placed on the heater! 

 

If other gas should be used to supply the heater, then it is required 

to perform conversion. These operations can be performed only by the 
authorized service of the manufacturer. The following conversions are 
possible: 

 

Heaters adapted for G20 gas can be converted to G27 and 
G2.350 gas, 

 

Heaters adapted for G31 can be converted to G30. 

The conversion is based on the following operations: 

 

Replacement  of  nozzle  of  primary  burner  with  the  one 
suitable for the used gas, 

 

Screw the bolt in to the burner injector, 

 

Perform  adjustment  acc.  to  the  instruction  in  6.8  choosing 
data  from  table  for  the  required  type  of  gas  and  model  of 
heater. 

After conversion, it is required to stick one of the delivered rating 

plates containing information on current type of gas.   

6.10.

 

INSTALLATION OF THE HEATER 

 

Room heater should be installed in compliance with the 
requirements of the currently applicable standards and 
legal regulations and detailed regulations of the country 
of destination. In Poland these conditions are regulated 
by the Regulation of the Minister of Infrastructure of 12 
April  2002  on  technical  conditions  which  should  be 
fulfilled by buildings and its location. (Journal of Laws 
no. 75 of 2002 item 690 as amended). 

 

If the DEFRO HOME VITAL heater is installed in rooms, 
where  particularly  exposed  people  (such  as  children, 
physically  disabled  or  people  requiring  special 
attention) may have contact with it, then it is required to 
use  additional  protections.  The  protections  are 
intended  to  prevent  contact  of  exposed  people  with 
operating and hot equipment. 

Fireplace  system  should  be  made  of  non-combustible  materials 

and  its  design  should  allow  disassembly  of  the  housing  and  heater 
without any damages. 

Installation  of  the  room  heater  should  obey  the  following  safety 

rules: 

 

minimum  distance  80  mm  from  side  and  rear  of  the  non-
flammable materials, 

 

minimum distance 400 mm from side and rear of the medium 
inflammable materials, 

 

minimum  distance  800  mm  from  front  wall,  where  the 
medium inflammable materials cannot be located, 

 

objects  made  of  highly  inflammable  materials  should  be 
located in distance minimum 2000 mm from furnace. 

If it is not possible to maintain the above indicated distances, then 

you should apply process and building measures to avoid fire hazards. 
In case of contact with wooden wall or wall made of other inflammable 
material, it is appropriate to insulate flue gas discharge pipe. 

 

In  case  of  floor  made  of  inflammable  materials,  it  is 
appropriate to prepare a plane protecting the floor and 
execute  protection  in  accordance  with  the  standards 
applicable in the given country. 

All surfaces of the equipment are working surfaces! 

The  room  heater should  be  located  on  a substrate  with  suitable 

load-bearing capacity. In accordance with the Polish Standards each 
square meter of the floor slab in a single-family building should transfer 
load  of  150  kg.  If  this  condition  is  fulfilled,  the  room  heater 
manufactured by DEFRO can be installed without needing to reinforce 
the floor slab.  

Nonetheless, if you are not sure about design of floor slab, where 

the heater is to be installed, you should absolutely contact with building 
designer  to  reinforce  the  floor  slab  or  execute  special  structure 
distributing the weight on larger area. 

The system, where the gas-fired room heater is installed, should 

be  equipped  with  air  supply  and  exhaust  grilles  of  corresponding 
surfaces.  They  are  intended  to  ensure  heat  transfer  between  the 
fireplace and the room. Supply grille should be located in bottom part 
of the system to ensure supply of the cold air from the room. Exhaust 
grille should be located in hood. For DEFRO HOME VITAL the size of 
supply  grille  should  be  lower  than  700  cm

2

  and  900  m

2

  for  exhaust 

grille. 

The room, where the DEFRO HOME VITAL room heater has been 

installed, should also be equipped with a supply/return grille to ensure 
exhaust  of  gas  in  the case  of  leaks in the  gas  piping system.  In the 
system, the exhaust grille should be located in a place depending on 
the fuel used in the fireplace. 

 

For natural gas (NG) the grille should be located under the 
ceiling. 

 

For propane-butane (LPG) the grille should be located near 
the floor, above the ground level. 

 

Picture 22. Minimum distance that should be kept during installation of 
the heater. 

ATTENTION!!! 
Lack  of  expansion joint may  be  a  reason of  equipment  damage 
what is connected with loss of the warranty rights.

 

6.11.

 

FIRST START-UP 

Perform leak-tightness test of gas connections to the gas 

unit and from gas unit to gas nozzle during operation of the 

equipment before first start-up. 

First  start-up  should  be  performed  by  the  fitter  after  checking 

correctness of installation.  

Odour  of  paint  from  the  body  will  be  released  during  the  first 

several  hours  of combustion.  This  is completely  normal. You should 
strongly vent the room at that time. Check tightness of joints once again 
when equipment has been cooled down. 

80 mm

housing

insulation made

of non-combustile materials

facade

of fireplace insert

wall

80 mm

80 mm

20-30 mm

Summary of Contents for VITAL 37S

Page 1: ...erating manual gas fired convection room heater DEFRO HOME VITAL 37 S 51 S BP BL U C T gas type G2 350 G20 G27 G31 G30 translation of original operating manual edition 1 b May 2021 destination countri...

Page 2: ...deklaracja musi by przekazana wraz z urz dzeniem w przypadku odst pienia w asno ci innej osobie This Declaration of Conformity becomes invalid if any changes have been made to the device if its constr...

Page 3: ...illed copy of the Warranty Card to the following address DEFRO Sp z o o Sp k Centrum Serwisowe Ruda Strawczy ska 103a 26 067 Strawczyn serwis defro pl By sending back your Warranty Card you will be re...

Page 4: ...2 Preparation 16 7 3 Information 16 7 4 Deactivation of remote control function 16 7 5 Activation of remote control function 16 7 6 Control of FIREPLACE with a remote control 16 7 6 1 Setting temperat...

Page 5: ...34 13 PRODUCT WARRANTY TERMS AND CONDITIONS 35 13 1 Warranty conditions 48h Service 36 14 WARRANTY CARD 37 15 CARRIED OUT WARRANTY REPAIRS AND MAINTENANCE 38 16 WARRANTY CARD copy to send back 39 17...

Page 6: ...m the action of high temperature Non compliance with the recommendations distinguished in this way may cause a fire or burns Hint Informative symbol Useful information and hints are marked in this way...

Page 7: ...The body of the heater is made of steel sheet with combustion chamber located inside and lined with additional panels made of sheet rear and sides Picture 1 Design of DEFRO HOME VITAL heater 1 explos...

Page 8: ...pply V DC 6 Weight1 kg 90 90 90 90 90 1 Device weight depends on selected design version and its equipment 2 Level for C11 equipment acc to PN EN 613 2002 A1 2004 Table 2 Technical data of GV60 regula...

Page 9: ...O HOME VITAL 51 S U Picture 8 Dimensions of DEFRO HOME VITAL 51 S T Picture 9 Dimensions of DEFRO HOME VITAL 51 S 983 47 808 330 297 150 883 370 115 98 111 783 188 350 828 309 781 370 107 98 154 720 4...

Page 10: ...ts pressure and whether the current settings of a heater are correct VITAL heater should be supplied with the same type of gas as the other gas fired equipment if any in the home of their installation...

Page 11: ...reduction of total allowable length of the pipe by 1 meter First elbow connected to the equipment is not taken into consideration Vertically lead pipes should be fixed to the wall using brackets arra...

Page 12: ...f the existing chimney in connection with a terminal should be protected against flooding or clogging and the terminal should be installed in a way ensuring its correct operation Penetration of concen...

Page 13: ...y burner by turning the screw clockwise rotation increases the pressure When the adjustment has beencompletedyoushouldprotect the following fixtures with blanking plugs pressure control screw and afte...

Page 14: ...tion of concentric coaxial system acc to allowed configuration for ducts leading set the flue gas flow damper in half of opening position Close the window panel and set maximum load of the heater Meas...

Page 15: ...of contact with wooden wall or wall made of other inflammable material it is appropriate to insulate flue gas discharge pipe In case of floor made of inflammable materials it is appropriate to prepar...

Page 16: ...control knob to ON Make sure that four 4 AA batteries have been correctly installed in the receiver Remote control operating at the 868 MHz band also requires preparation You should enter the transmi...

Page 17: ...tton firing with one button on remote control or two button and at the same time firingup with two buttons until twoshort audible signals will be heard and an icon confirming the ignition will be flas...

Page 18: ...what temperature should be maintained Eco mode controls the fireplace so as to maintain the set temperature but inthemore economical way Thecontroller forces maximum height of the flame if thetempera...

Page 19: ...ed once again for a while and minutes field will be flashing Select minutes using buttons Confirm the setting once again with the button The system will go to configuration of switch off time Switch o...

Page 20: ...in manual control mode All operations are then performed directly from the GV60 valve level located inside the cabinet Control components used during manual control are presented on the picture 24 To...

Page 21: ...ion locked for two minutes Second thermocouple in incorrect position Incorrect connection of cables of the second thermocouple Decorative items installed incorrectly Clogged openings of the primary bu...

Page 22: ...ange of settings No flame control from controller level No WiFi connection with WiFi module of the controller Switched off WiFi connection on the control device F42 Check WiFi Flame does not respond t...

Page 23: ...omponents should not touch the window panel Components should not cover the flame of the control burner It is forbidden to cover outlet holes of the primary burner and gaps in the floor of the combust...

Page 24: ...installation of chunks 2 Lay item no 1 as presented on both photos The component should remain stable at the centre of the ignition burner and parallel to the rear wall The wider end of thechunk shoul...

Page 25: ...th photos Chunk should be stable due to incisions adapted to the burner The distance between the holes in the burner and the edge of the chunk should be approx 5 mm right corner of the burner the edge...

Page 26: ...c to the incision and photos Similarly as for chunk no 2 the distance between the holes in the burner and the edge of the chunk should be approx 5 mm left corner of the burner the edge of the ceramic...

Page 27: ...27 5 Lay chunk no 4 as presented on the photos The chunk should not cover burner openings and should be supported in half way on chunk no 1 gas holes...

Page 28: ...28 gas holes left corner of the burner...

Page 29: ...29 6 Lay item no 5 as presented on photos The chunk should be stable and should not cover gas openings in the floor right corner of the burner gas gaps...

Page 30: ...30 7 Set the chunk no 6 as the last one it should be laid on chunk no 5 and be supported on chunk no 4 and right corner of the burner...

Page 31: ...31 right corner of the burner...

Page 32: ...32 8 3 LAYING OF DECORATION IMITATING THE STONES Items made of stone should be laid on the floor of the combustion chamber so as to avoid covering of gas openings...

Page 33: ...or this purpose they should not be used on other surfaces or components e g painted because they may damage them 9 2 WINDOW PANEL DISMANTLING To clean the window panel combustion chamber or install de...

Page 34: ...arbon monoxide is a result of defect or leaks in the system Given the impossibility to detect presence of this hazardous gas you should Perform inspections of the system and its maintenance by authori...

Page 35: ...pr assembly of window panels iv decorative items supplied with the equipment or purchased by the customer v all damages resulting from incorrect transport from distributor to the customer incorrect i...

Page 36: ...accept the claim and to charge its costs to buyer 25 Provisions of this document shall not limit in any way the rights resulting from the claim filed based on the statutory guarantee The warranty doe...

Page 37: ...s been delivered as complete the device showed no failure during the first start up carried out by a service company has received the Operating Manual and equipment s installation manual with this War...

Page 38: ...38 15 CARRIED OUT WARRANTY REPAIRS AND MAINTENANCE No date fault description repaired element description of repairs comments Stamp and signature of Service 1 2 3 4 5 6 7 8 9 10...

Page 39: ...s been delivered as complete the device showed no failure during the first start up carried out by a service company has received the Operating Manual and equipment s installation manual with this War...

Page 40: ...40...

Page 41: ...technician Way of fault removal Advice DESCRIPTION END OF COMPLAINT Name and surname of service technician Fault removal date Justness of complaint Duration of repair Fault defect has been removed th...

Page 42: ......

Page 43: ...hnician Way of fault removal Advice DESCRIPTION END OF COMPLAINT Name and surname of service technician Fault removal date Justness of complaint Duration of repair Fault defect has been removed the eq...

Page 44: ......

Page 45: ...technician Way of fault removal Advice DESCRIPTION END OF COMPLAINT Name and surname of service technician Fault removal date Justness of complaint Duration of repair Fault defect has been removed th...

Page 46: ......

Page 47: ...47 20 REGISTER OF INSPECTIONS OF SMOKE DUCTS date stamp and signature of chimneysweep date stamp and signature of chimneysweep...

Page 48: ...mbol Unit value Heat output Rated heat output Pnom kW 6 0 Minimum heat output Pmin kW 3 6 Performance Performance at rated thermal power th nom Performance at minimal thermal power indicative th min A...

Page 49: ...ol Unit Value Heat output Rated heat output Pnom kW 5 5 Minimum heat output Pmin kW 3 3 Performance Performance at rated thermal power th nom Performance at minimal thermal power indicative th min Aux...

Page 50: ......

Page 51: ...51...

Page 52: ...509 702 720 509 577 900 DEFRO Sp ka z ograniczon odpowiedzialno ci Sp ka komandytowa 00 403 Warszawa ul Solec 24 253 Production plant Ruda Strawczy ska 103 A 26 067 Strawczyn tel 41 303 80 85 biuro d...

Reviews: