C _ _ _ SERIAL DATA SOURCE
scrolls across the display and toggles with the cur-
rently selected serial data source. Using the
and
buttons, select:
DISP
,
TEMP 1
,
TEMP 2
,
TEMP 3
,
TEMP 4
,
AVETMP
,
MAXTMP
,
MINTMP
,
PEAK
, or
VALLEY
, and then press
.
Note that your options in this step will be limited by the 'Number of Sensors' selected in 6.2D.
See Section 5 for more information about serial data sources.
D _ _ _ BAUD RATE
scrolls across the display and toggles with the current se-
lection. Use the
and
buttons to select one of:
1200
,
2400
,
4800
,
9600
,
19200
,
38400
,
57600
or
115200
. Then press
.
E
_ _ _ PARITY
scrolls across the display and toggles with the currently selected
parity. Using the
and
buttons, select:
NONE
,
ODD
or
EVEN
, and then
press
.
F
_ _ _ SERIAL ADDRESS
scrolls across the display and toggles with the currently
selected serial address. Use the
and
buttons to alter the serial address,
and then press
.
The serial address parameter is used to identify a particular device when it is used with other
devices in a system. (It applies particularly to
MODBUS
mode when used on an RS485 serial
network.) The serial address of the controller must be set to match the serial address defined
in the master device.
6.8 - Edit F1 PIN number
A _ _ _ EDIT F1 PIN NUMBER
scrolls across the display and toggles with
SKIP
.
Press
to skip and return to the operational display, or the
button and
then
to
ENTER
and change your PIN number.
B _ _ _ ENTER NEW F1 PIN NUMBER
scrolls across the display and toggles with
the current PIN (default 1). Using the
and
buttons, enter your new F1 PIN
number. Then press
to exit to the operational display.