8.8 - Edit CAL PIN number
A
_ _ _ EDIT CAL PIN NUMBER
scrolls across the display, and
SKIP
appears. Press
to skip and return to the operational display, or the
button and then
to
ENTER
and change your PIN number.
B
_ _ _ ENTER NEW CAL PIN NUMBER
scrolls across the display, and the current
PIN (default 1) appears. Using the
and
buttons, enter your new CAL PIN
number. Then press
to exit to the operational display.
9
SETPOINT SETUP
The soft ware in your controller will allow you to confi gure 1 batch setpoint (SP 1)
and 3 standard setpoints (SP 2–4). SP 5 may be used as an LED indicator, if desired.
SP 6 is reserved.
Setpoints with no corresponding relay output hardware may be used as simple LED
indicators, if desired. In this case, features requiring relay output functionality will
continue to appear in the setup menu, but will be ignored by the controller.
9.1 - Enter SP PIN number
A
Enter setpoint setup mode by pressing and holding the
button for 3 seconds.
_ _ _ ENTER SP PIN NUMBER
scrolls across the display, and
0
appears. Use the
and
buttons to enter your security code (factory default 1). Then press
. If the correct PIN is entered, setup is started at 9.2.
If an incorrect PIN number is entered,
_ _ _ INCORRECT PIN NUMBER – ACCESS
DENIED
scrolls across the display, and it returns to normal operating mode.
You will have the opportunity to change your PIN number at the end of this section
(9.3). If you have forgotten your PIN number, see Section 11.