![DEEP SEA ELECTRONICS DSEControl DSEE050 Operator'S Manual Download Page 34](http://html.mh-extra.com/html/deep-sea-electronics/dsecontrol-dsee050/dsecontrol-dsee050_operators-manual_2463070034.webp)
Maintenance, Spares, Repair & Servicing
057-300 ISSUE: 1.1
Page 34 of 36
6.2 DSEE050 CONFIGURATION HARNESS (016-177)
NOTE: DSEE050 Configuration Harness 016-177 must be used in conjunction with Peak
Systems USB CAN interface IPEH-002021 or IPEH-002022 from https://www.peak-system.com
DSE Part 016-177 consists of a minimal cable with connector fitted at one end with DC supply wires
and DE9 CAN connector at the other end. This is designed to connect to the DE9 connector of the
USB CAN interface.
Description
Connector A
Termination
DC Positive
7
Single wire
DC Negative
1
Single wire
CAN SCR
2
DE9 Pin 5
CAN L
3
DE9 Pin 2
CAN H
4
DE9 Pin 7
6.3 PCAN-USB CONNECTION DETAILS
NOTE: Where a DSE Configuration or Connection Harness is not used, connection details
for PCAN-USB are shown below. PCAN-USB supplier details are given in the section entitled
Maintenance Spares, Repair and Servicing elsewhere in this document.
NOTE: DSE Stock and supply PCAN-USB IPEH-002021. DSE Part number 016-179. Contact
Connect PCAN-USB to DSEE050 using connections for CAN H, CAN L and GND. For suitable
connection looms from DSE, see DSE Publication
057-300 DSEE050 Operator Manual.
Shown looking at the PCAN-
USB interface from the ‘outside’
Connector A
Deutsch
DT16-18SA-K004
Cable Ident.
Length 2 m ( 3 ’ 3 “)
DE9 Female
Connector
Clearly marked DC Supply
connections
Length 1 m
(6’ 6.7 “)