![DEEP SEA ELECTRONICS DSEControl DSEE050 Operator'S Manual Download Page 29](http://html.mh-extra.com/html/deep-sea-electronics/dsecontrol-dsee050/dsecontrol-dsee050_operators-manual_2463070029.webp)
Commissioning
Page 29 of 36
057-300 ISSUE: 1.1
.
4.1.3.2
ICONS
NOTE: This section documents the Factory (Default) settings of the DSEE050. Due to the
configurable nature of the device this is subject to change as required by the supplier. Contact
supplier or consult the device configuration source for full details of the configured Icons.
NOTE: The Factory Settings for the Icons rely on Factory Settings for the relevant SPNs
within CAN Receive. Removing or changing the relevant SPNs in CAN Receive will prevent
correct operation of the Factory Set Icons.
NOTE: The Factory Settings for the Icons use a grey colour of the icon to mean Inactive.
Yellow, Red and White Icons are used to show Active status as detailed below.
Display
Description
Diagnostic Lamps. See section entitled
Lamps
for details.
Engine ECU Red Stop Lamp (SPN 623) is active.
Engine ECU Amber Stop Lamp (SPN 624) is active.
Aftertreatment 1 Diesel Particulate Filter Soot Load Percent
is reporting
High,
Most Severe.
(SPN 3719, FMI 0)
Aftertreatment 1 Diesel Particulate Filter Soot Load Percent
is reporting
High,
Moderate.
(SPN 3719, FMI 16)
Steady:
Diesel Particulate Filter Regeneration is not needed.
(SPN 3697, FMI 1)
Flashing Slow (1 Hz):
Diesel Particulate Filter Regeneration is reporting
Service Level
.
(SPN 3697, FMI 4)
Diesel Particulate Filter Regeneration is Inhibited.
(SPN 3703, FMI 0)
Steady:
Diesel Exhaust Fluid is Low.
(SPN 3517, FMI 1)
Flashing Slow (1 Hz):
Diesel Exhaust Fluid is very low.
(SPN 3517, FMI 4)
Steady:
SCR Anomaly. Operator Warning System Active.
(SPN 5246, FMI 1)
Flashing Slow (1 Hz):
SCR Anomaly. Low Level Inducement Enabled or
Active.
(SPN 5246, FMI 2 or FMI 3)
Continued Overleaf.