To prevent damage to the collectors and their connections by frost
and corrosion, it is essential that a high quality heat transporting fluid
be used to fill the solar installation. If the recommended ready-mixed
fluid is used (Tyfocor L / LS) the system will be adequately protected
at temperatures down to approx. -24 °C.
To prevent any damage of the system,
pressure tests
should only
be carried out with the
heat-transporting fluid
used later on.
4
Testing pressure: 4 bar
4
Test time:
minimum 1 hour
4
Pressure gauge
39
Filling pump
61
Thermometer
84
Stop valve with lockable nonreturn valve
85
Primary solar circuit pump
87
Sealed safety valve calibrated at 6 bar
88
Solar expansion vessel
89
Heat transfer fluid container
112b
Domestic hot water sensor
114
Primary solar circuit filling and draining device
(
a
propylene glycol)
126
Solar regulator
130
Manual bleed degasser
131
Array of collectors
132
Solar station complete with DIEMASOL solar regulation
M001774-B
130
89
89
230V
50Hz
114
61
88
87
85
4
84
114
39
61
61
4. Installation
NEO 2.1 / SUN 211
39
05/10/09 - 300020210-001-B
Summary of Contents for NEO 2.1
Page 4: ...3 05 10 09 300020210 001 B ...
Page 20: ...M001777 A I M001778 A 4 Installation NEO 2 1 SUN 211 19 05 10 09 300020210 001 B ...
Page 26: ...3 4 5 M001766 A 4 Installation NEO 2 1 SUN 211 25 05 10 09 300020210 001 B ...
Page 29: ...n Solar Panel Connection M001769 A NEO 2 1 SUN 211 4 Installation 05 10 09 300020210 001 B 28 ...
Page 32: ...2 3 M001784 A 4 Installation NEO 2 1 SUN 211 31 05 10 09 300020210 001 B ...
Page 35: ...n Solar Panel Connection M001787 A NEO 2 1 SUN 211 4 Installation 05 10 09 300020210 001 B 34 ...