Faults
Code Cause
of the
error
Description
Checking / solution
AUX.SENS.FAIL.
D07
SCU
Auxiliary sensor failure
Bad connection
4
Check whether the sensor is connected:
¼
See chapter: "Deletion of sensors from the
4
Check the link and the connectors
4
Check that the sensor has been correctly fitted
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
DHW S.FAILURE
D09
SCU
Domestic hot water sensor
failure
Remarks:
Heating of domestic hot water
is no longer ensured.
The load pump operates.
The load temperature of the
dhw tank is the same as the
boiler.
Bad connection
4
Check whether the sensor is connected:
¼
See chapter: "Deletion of sensors from the
4
Check the link and the connectors
4
Check that the sensor has been correctly fitted
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
ROOM S.A FAIL.
ROOM S.B FAIL.
ROOM S.C FAIL.
D11
D12
D13
SCU
Fault room temperature sensor
A
Fault room temperature sensor
B
Fault room temperature sensor
C
Note:
The circuit concerned operates
without any influence from the
room sensor.
Bad connection
4
Check whether the sensor is connected:
¼
See chapter: "Deletion of sensors from the
4
Check the link and the connectors
4
Check that the sensor has been correctly fitted
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
MC COM.FAIL
D14
SCU
Communication failure
between the SCU PCB and the
boiler radio module
Bad connection
4
Check the link and the connectors
Boiler module failure
4
Change the boiler module
ST.TANK S.FAIL
D15
SCU
Storage tank sensor failure
Note:
The hot water storage tank
reheating operation is no
longer assured.
Bad connection
4
Check whether the sensor is connected:
¼
See chapter: "Deletion of sensors from the
4
Check the link and the connectors
4
Check that the sensor has been correctly fitted
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary