Faults
Code Cause
of the
error
Description
Checking / solution
BL OPEN FAIL
L39
PCU
The
BL
inlet opened for a short
time
Bad connection
4
Check the wiring
External cause
4
Check the device connected to the
BL
contact
Parameter incorrectly set
4
Check the parameter
IN.BL
TEST.HRU.FAIL
L40
PCU
HRU/URC unit test error
Bad connection
4
Check the wiring
External cause
4
Suppress the external cause
Parameter incorrectly set
4
Check the parameters
DEF.WATER MIS.
L250
PCU
The water pressure is too low Hydraulic circuit incorrectly vented
Water leak
Measurement error
4
Top up with more water if necessary
4
Reset the boiler
MANOMETRE FAIL L251
PCU
Pressure gauge fault
Wiring problem
The manometer is defective
Sensor pcb defective
4
Check the wiring between the PCU PCB and the
pressure gauge
4
Check whether the pressure gauge has been
correctly fitted
4
Replace the pressure gauge if need be
OUTL S.B FAIL.
OUTL S.C FAIL.
D03
D04
SCU
Sensor fault flow circuit B
Sensor fault flow circuit C
Remarks:
The circuit pump is running.
The 3-way valve motor on the
circuit is no longer powered
and can be adjusted manually.
Bad connection
4
Check whether the sensor is connected:
¼
See chapter: "Deletion of sensors from the
4
Check the link and the connectors
4
Check that the sensor has been correctly fitted
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
OUTSI.S.FAIL.
D05
SCU
Fault external sensor
Remarks:
The boiler operates on
BOILER MAX
temperature.
The valve setting is no longer
ensured but monitoring the
maximum temperature of the
circuit after the valve is
ensured.
Valves may be manually
operated.
Reheating the domestic hot
water remains ensured.
Bad connection
4
Check whether the sensor is connected:
¼
See chapter: "Deletion of sensors from the
4
Check the link and the connectors
4
Check that the sensor has been correctly fitted
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
8. Troubleshooting
MCA 15 - MCA 25 MCA 25/28 MI
120