Connect the DHW tank anode.
If the tank is not fitted with an impressed current
anode, put the simulation connector in place
(delivered with the DHW sensor - package
AD212).
O
Do not connect anything to the terminal block.
Settings to be made for this type of installation
Parameters
Access
Settings to be made See chapter
INSTALLATION
"Installer" level
#SYSTEM
menu
EXTENDED
¼
"Displaying the parameters in extended mode", page
I.SYST
(1)
"Installer" level
#SYSTEM
menu
STORAGE TANK
¼
"Setting the parameters specific to the installation",
O.DHW:
(1)
"Installer" level
#SYSTEM
menu
PUMP
(1) The parameter is only displayed if
INSTALLATION
parameter is set to
EXTENDED
The DHW part is maintained at the DHW set point by the
boiler.
The heating zone is maintained at the set temperature
calculated according to the outside temperature. The zone
is reheated when the heating buffer temperature sensor
falls -6°C below the calculated set temperature. Reheating
in the heating zone stops when the heating buffer
temperature rises above the calculated set temperature.
n
PS storage tank and DHW tank connected to the storage
tank
The boiler only starts up production of domestic hot water if the
storage tank is not hot enough to guarantee tank loading.