Faults
Code Cause
of the
error
Description
Checking / solution
SWIM.P.B. S.FAIL
SWIM.P.C. S.FAIL
D16
D16
SCU
Swimming pool sensor failure
circuit B
Swimming pool sensor failure
circuit C
Note:
Pool reheating is independent
of its temperature.
Bad connection
4
Check whether the sensor is connected:
¼
See chapter: "Deletion of sensors from the
4
Check the link and the connectors
4
Check that the sensor has been correctly fitted
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
DHW 2 S.FAIL
D17
SCU
Sensor failure tank 2
Bad connection
4
Check whether the sensor is connected:
¼
See chapter: "Deletion of sensors from the
4
Check the link and the connectors
4
Check that the sensor has been correctly fitted
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
PCU COM. FAIL
D27
SCU
Communication failure between the SCU and PCU PCBs
4
Check the wiring between the SCU and PCU PCBs
4
Check that the PCU PCB is powered up (green LED on or flashing)
4
Change the PCU PCB
IOBL.3WV B DEF
D29
SCU
Communication failure
between the SCU PCB and the
V3V module
The V3V module is switched off
4
Check that the 3WV module is powered up (Green
LED LIT)
The V3V module and the SCU PCB are not connected
to the same live terminal
4
Check that the 3WV module and the SCU PCB are
on the same live terminal or that a live coupler is
installed
The V3V module has been removed
IOBL.3WV C DEF
D30
SCU
Communication failure
between the SCU PCB and the
V3V module
The V3V module is switched off
4
Check that the 3WV module is powered up (Green
LED LIT)
The V3V module and the SCU PCB are not connected
to the same live terminal
4
Check that the 3WV module and the SCU PCB are
on the same live terminal or that a live coupler is
installed
The V3V module has been removed
COM.IOBL FAIL.
D31
SCU
The IOBL function is no longer
active
Problem on the SCU PCB
4
If the IOBL function is not used, deactivate the
IOBL function in the menu
#CONFIGURATION
4
If the IOBL function is used, change the SCU PCB
and re-pair the devices (IOBL 3WV module,
Interscenario switch)
8. Troubleshooting
MCA 15 - MCA 25 MCA 25/28 MI
122
29/04/2010 - 300022146-001-B