Tab.6
Heating mode: outdoor air tempe2 °C, water temperature at the 35 °C. Performances in accordance
with EN 14511-2.
Measurement type Unit
AWHP 4.5
MR
AWHP 6
MR-3
AWHP 8
MR-2
AWHP 11
MR-2
AWHP 11
TR-2
AWHP 16
MR-2
AWHP 16
TR-2
Heat output
kW
3.47
3.74
6.8
10.19
10.19
12.90
12.90
Coefficient of Per
formance (COP)
3.97
3.37
3.3
3.20
3.20
3.27
3.27
Absorbed electri
cal power
kWe
0.88
1.11
2.06
3.19
3.19
3.94
3.94
Tab.7
Cooling mode: outdoor air tempe35 °C, water temperature at the 18 °C. Performances in accordance
with EN 14511-2.
Measurement type Unit
AWHP 4.5
MR
AWHP 6
MR-3
AWHP 8
MR-2
AWHP 11
MR-2
AWHP 11
TR-2
AWHP 16
MR-2
AWHP 16
TR-2
Cooling output
kW
3.80
4.69
7.90
11.16
11.16
14.46
14.46
Energy efficiency
ratio (EER)
4.28
4.09
3.99
4.75
4.75
3.96
3.96
Absorbed electri
cal power
kWe
0.89
1.15
2.00
2.35
2.35
3.65
3.65
Tab.8
Common specifications
Measurement type Unit
AWHP 4.5
MR
AWHP 6
MR-3
AWHP 8
MR-2
AWHP 11
MR-2
AWHP 11
TR-2
AWHP 16
MR-2
AWHP 16
TR-2
Power voltage of
the outdoor unit
V
230
230
230
230
400
230
400
Start-up amperage A
5
5
5
5
3
6
3
Maximal amper
age
A
12
13
17
29.5
13
29.5
13
Refrigerant fluid
R410A
kg
1.3
1.4
3.2
4.6
4.6
4.6
4.6
R410A refriger
tCO
2
e
2.714
2.923
6.680
9.603
9.603
9.603
9.603
Refrigerant con
nection (Liquid -
Gas)
inch
1/4 - 1/2
1/4 - 1/2
3/8 - 5/8
3/8 - 5/8
3/8 - 5/8
3/8 - 5/8
3/8 - 5/8
Max. pre-charged
length
m
7
10
10
10
10
10
10
(1) The quantity of refrigerant in CO
2
equivalent is calculated using the following formula: quantity (in kg) of refrigerant x GWP / 1000. The
Global-Warming Potential (GWP) of R410A gas is 2088.
3.2.3
Heat pump weight
Tab.9
Indoor module
Indoor module
Unit
MIV-S 4-8/EM
MIV-S 4-8/EMI
MIV-S 4-8/H
MIV-S 4-8/HI
Weight (empty)
kg
35.5
36.7
36.1
38.2
Tab.10 Indoor module
Indoor module
Unit
MIV-S
11-16/EM
MIV-S
11-16/EMI
MIV-S
11-16/ET
MIV-S
11-16/ETI
MIV-S
11-16/H
MIV-S
11-16/HI
Weight (empty)
kg
35.5
36.7
35.5
36.7
36.1
38.2
3 Technical specifications
7748711 - v03 - 08062020
AWHP MIV-S
13