3 Technical specifications
3.1
Certifications
CE identification no
CE-0085CM0178
NOx classification
5 (EN 15502-1, EN 15502-2-1)
Type of connection Chimney: B
23
, B
33
Flue gas outlet: C
13(x)
, C
33(x)
, C
43(x)
, C
53
, C
83(x)
,
C
93(x)
3.2
Technical specifications
Boiler type
AGC 10/15 AGC 15
AGC 25
AGC 35
General
Nominal output (Pn)
Heating System (80/60 °C)
minimum-
maximum
kW
3,0 - 10,4
3,0 - 14,9
5,0 - 24,8
6,3 - 34,8
Nominal output (Pn)
Heating System (50/30 °C)
minimum-
maximum
kW
3,4 - 11,2
3,4 - 15,8
5,6 - 25,5
7,0 - 35,9
Nominal output (Pn)
Heating System (40/30 °C)
minimum-
maximum
kW
3,4 - 16,0
3,4 - 16,0
5,6 - 25,9
7,0 - 36.4
Nominal input (Qn)
Heating System (Hi)
minimum-
maximum
kW
3,1 - 10,5
3,1 - 15,0
5,2 - 25,0
6,5 - 35,1
Nominal input(Qn)
Heating System (Hs)
minimum-
maximum
kW
3,4 - 11,7
3,4 - 16,7
5,8 - 27,8
7,2 - 39,0
Nominal input (Qnw)
DHW System (Hi)
minimum-
maximum
kW
3,1 - 15,0
3,1 - 15,0
5,2 - 29,3
6,5 - 35,1
Nominal input (Qnw)
DHW System (Hs)
minimum-
maximum
kW
3,4 - 16,7
3,4 - 16,7
5,8 - 32,6
7,2 - 39,0
Heating efficiency under full load (Hi)
(80/60 °C)
-
%
99,3
99,3
99,2
99,1
Heating efficiency under full load (Hi)
(50/30 °C)
-
%
107,0
105,3
102,0
102,2
Heating efficiency under partial load
(Hi) (Return temperature 60°C)
-
%
94,9
94,9
96,1
96,3
Heating efficiency under partial load
(EN 92/42) (Return temperature
30°C)
-
%
110,2
110,2
110,1
110,6
Data on the gases and combustion gases
Gas consumption - Natural gas H
(G20)
minimum-
maximum
m
3
/h
0,33 - 1,59 0,33 - 1,59 0,55 - 3,10 0,69 - 3,71
Gas consumption - Natural gas L
(G25)
minimum-
maximum
m
3
/h
0,38 - 1,85 0,38 - 1,85 0,64 - 3,61 0,80 - 4,32
Gas consumption - Propane G31
minimum-
maximum
m
3
/h
0,13 - 0,61 0,13 - 0,61 0,21 - 1,20 0,27 - 1,44
Mass flue gas flow rate
minimum-
maximum
kg/h
5,3 - 25,2
5,3 - 25,2
8,9 - 49,3
11,1 - 57,3
AGC 10/15 AGC 15 AGC 25 AGC 35