5.3
Changing the settings
5.3.1.
Setting the set point temperatures
C
Menu
Parameter
Adjustment range Description
Factory setting
DAY TEMP.A
5 to 30 °C
Desired room temperature in comfort periods on circuit A
20 °C
NIGHT TEMP.A
5 to 30 °C
Desired room temperature in reduced periods on circuit A
16 °C
DAY TEMP.B
(1)
5 to 30 °C
Desired room temperature in comfort periods on circuit B
20 °C
NIGHT TEMP.B
(1)
5 to 30 °C
Desired room temperature in reduced periods on circuit B
16 °C
DAY TEMP.C
(1)
5 to 30 °C
Desired room temperature in comfort periods on circuit C
20 °C
NIGHT TEMP.C
(1)
5 to 30 °C
Desired room temperature in reduced periods on circuit C
16 °C
DHW TEMP.
(1)
10 to 80 °C
Desired domestic hot water temperature in the DHW circuit
55 °C
TEMP.TANK AUX
(1)
10 to 90 °C
Desired domestic hot water temperature in the auxiliary circuit 55 °C
DHW A TEMP.
(1)
10 to 90 °C
Desired domestic hot water temperature in circuit A
55 °C
TEMP.SOL.TANK
(1)
(2)
20 to 80 °C
Maximum load temperature of the tank’s solar zone
65 °C
SWIMMING P.T.B
(1)
HG / 0.5 to 39 °C
Desired temperature for swimming pool B
20 °C
SWIMMING P.T.C
(1)
HG / 0.5 to 39 °C
Desired temperature for swimming pool C
20 °C
WATER T.NIGHT
10 to 80 °C
Desired domestic hot water temperature in the DHW circuit
10 °C
WATER T.NIGHTAUX
10 to 90 °C
Desired domestic hot water temperature in the auxiliary circuit 10 °C
WATER T.NIGHT.A
10 to 90 °C
Desired domestic hot water temperature in circuit A
10 °C
(1) The parameter is only displayed for the options, circuits or sensors actually connected.
(2) The menu is only displayed if the solar control system is connected
5.3.2.
Selecting the operating mode
To select an operating mode, proceed as follows:
1. Press the
MODE
key.
2. To select the desired parameter, turn the rotary button.
3. To modify the parameter, press the rotary button.
To go back to the previous display, press the key
j
.
4. To modify the parameter, turn the rotary button.
5. To confirm, press the rotary button.
To cancel, press key
h
.
MODE
C002267-A
5. Operating the appliance
AGC 10/15 AGC 15 AGC 25 AGC 35
21