Parameters
Description
Factory setting
Customer setting
PERMUT
Used to establish the pilot heat pump:
AUTO : the pilot heat pump automatically switches every 7
days
Can be set from 1 to 10: number of the heat pump chosen
as the pilot heat pump
AUTO
CALIBR.ROOM A
Calibration of the room temperature sensor on circuit A.
Make this setting 2 hours after switching on, when the room
temperature has stabilised.
Room tempera
ture on circuit A
CALIBR.ROOM B
Calibration of the room temperature sensor on circuit B.
Make this setting 2 hours after switching on, when the room
temperature has stabilised.
Room tempera
ture on circuit B
CALIBR.ROOM C
Calibration of the room temperature sensor on circuit C.
Make this setting 2 hours after switching on, when the room
temperature has stabilised.
Room tempera
ture on circuit C
ANTIFR.ROOM A
Room temperature at which frost protection on circuit A is ac
tivated.
Can be set from 0.5 to 20°C.
6°C
ANTIFR.ROOM B
Room temperature at which frost protection on circuit B is ac
tivated.
Can be set from 0.5 to 20°C.
6°C
ANTIFR.ROOM C
Room temperature at which frost protection on circuit C is
activated.
Can be set from 0.5 to 20°C.
6°C
#TIME .DAY menu - User Level
Tab.22 Menu #TIME .DAY
Parameters
Description
Factory setting
Customer setting
HOURS
Hours.
Can be set from 0 to 23.
MINUTE
Minutes.
Can be set from 0 to 59.
DAY
Day of the week.
Can be set from Monday to Sunday.
DATE
The day's date.
Can be set from 1 to 31.
MONTH
Month.
Can be set from January to December.
YEAR
Year.
Can be set from 2014 to 2099.
SUM.TIME
AUTO :
Automatic switch to summer time on the last Sunday in
March
Automatic switch to winter time on the last Sunday in
October
MANU :
For countries where the time change is done on other
dates or is not in use
AUTO
6.2
Setting the parameters
6.2.1
Setting the time and date
1. Go to the User level by pressing the
key.
2. Select the #TIME .DAY parameter by turning the settings button.
6 Settings