CONTROLLER FUNCTIONALITY
The controller offers the following control functions:
• Settable minimum and maximum frequency and open circuit voltage.
• Display of operating parameters including frequency, voltage, amperage, input
power and pump speed.
• Display of historical data including energy generation, maximum power and
operating times.
• Protection against over and under voltage, over current, system overload and
module over temperature.
• Fault detection with error code display.
• Selectable hybrid modes that prioritise solar supply as well as maximise output
through optimal blending of both power supplies
INSTALLATION
Dayliff Sunverter 3 controllers are surface mounted and should be provided with a
housing for water and heat protection. They must also be provided with a circuit
breaker between the PV modules and controller. Due to the high operating voltages
proper earthing is essential, which must be done by a qualified electrician. As a rule, all
PV powered solar pumping systems should be provided with a solar module array with a
nominal output about 30% greater than the motor size. In hybrid applications, higher
array MPP voltage is specified to allow achievement of larger solar supply share of
hybrid power supply. The arrays should be wired in a combination of series and parallel
connections to ensure that the correct voltage is available into the inverter. It is
important that the connection arrangement is approved by the pump supplier.
OPERATING CONDITIONS
0
0
Ambient Temperature:
-20 C to 60 C
Frequency
: 0-60Hz
Relative Humidity:
0-90% (Non-Condensing)
Altitude:
0-2000m***
CONTROLLER DATA
Model
Motor
Rated
Power
(kW)
Output
Rated AC
Current
(A)
5.5
3.7
2.2
3.0
11
15
18.5
22
Weight
(kg)
SV3/7.5T
SV3/11T
SV3/15T
SV3/18T
SV3/3.7M
SV3/5.5T
Dimensions (mm)
W
H
D
17
9
13
18
24
30
39
45
315
458
300
143
175
5.5
8
11.5
Max
DC
Input
Voltage
VDC
450
850
500-700
SV3/3.7T
1.1
SV3/1.5M
8.6
150-360
1.5
SV3/2.2M
Rated
Voltage
3x415V
1x240V
11
310-370
219
MPP
Voltage
VDC,
Solar
MPP
Voltage
VDC,
Hybrid
600-700
150-360
324-370
SV3/22T
***
If the altitude is over 2,000m, the rated output current of the inverter should be derated by 10% for every 1500m increase in height.
Rated
AC
Input
(A)
22.5
17.5
35
12
30
39
45
54
14
23
Current
416
257
158
Summary of Contents for SUNVERTER 3