24
Number
Name
Description
Factory
Set
Value
Scope
Pr.13
Maximum
Operating
frequency
To protect the motor load, maximum operating
frequency must be same as rated frequency of
motor.
Associated with the output V/F curve
0.01-60.00
50.00Hz
Pr.14
Weak light
frequency
0-60.00
Once the output frequency is less than the set
value and continuously lasts for a period (set value
of Pr.25), the inverter will enter weak light
protection and report as too dark.
Unit:Hz
30.00Hz
Pr.12
Reference
Frequency
0-Pr.13
Target frequency when Pr.7 is O. Unit: Hz
30.00Hz
Pr.15
Terminal 11
Function
0-9
0: Invalid
1: run/stop control, open-circuit to run, short-
circuit to stop.
2: run/stop control, open-circuit to stop, short-
circuit to run.
6: Source low signal, open-circuit is abnormal,
short-circuit is normal.
7: Tank full signal, open-circuit is normal, short-
circuit is abnormal.
8: Valid when I1&I2(or I3&I4) are used as group
for double source low signals, both input are
open-circuit is abnormal, both input are short-
circuit is normal.
9: Valid when I1&I2(or I3&I4) are used as group
for double tank full signals, both input are
open-circuit is normal, both input are short-
circuit is abnormal.
Others:
Other value settings are forbidden, or
else can cause abnormal operation
Note:
11&I2, I3&I4 are group terminals,
support linkage use or separate use.
When Pr.15 or Pr.17 is set to 8 or 9, Pr.16 or
Pr.18 value setting will be invalid.
7
Pr.16
Terminal 12
Function
Pr.17
Terminal 13
Function
Pr.18
Terminal 14
Function
0
6
0
Pr.19
Terminal 15
Function
0-3
0:Invalid
1:run/stop control, open-circuit to run, short-
circuit to stop
2:run/stop control, open-circuit to stop, short-
circuit to run.
3:Water flow detection, work with flow detection
unit setting parameters.
3