M12-Female Connector
1.
PWR+ (RED)
: 8...50 VDC
3. GND (BLACK): 0 VDC, Ground
2.
A (White) :
Output 4-20mA
4.
B (Green)
: Not Using
Each cable includes wires which are marked labels according to types of connection. (user should not cut these labels
before installation to avoid confusing)
Red:
PWR+(8...50VDC)
Black: PWR-(OVDC)
Green:
Not Using
White:
Output 4-20mA
Recommend to use 24VDC power.
The signal cable from sensor should be protected by corrugated hose or the Φ16 plastic tube, keep the cable avoid
high temperature areas.
Depending on the type of oil tank, we have different calibration of the corresponding oil quantity. Refer to the excel file
below to calculate the volume
PulseCAP10 with 4-20mA Output has an advanced feature is Field Calibration. Field Calibration allows customers to
calibrate the sensor after cutting. It will works with many non-conductive media such as Vegetable Oil, Non-standard
Diesel, Light Fuel Oil... To enter Calibration Mode: press the CALIB button on top housing 3 times, time interval
between press not greater than 1.5 seconds. LED will blinked at 5Hz in Calibration mode.
10.2 Follow Labels on Wires
10.3 Follow Wire Colors
11. Configuration
11.1 Calculate 4-20mA of oil tank
EXCEL FILE CALCULATE VOLUME OF OIL TANK
11.2 Calibration 4-20mA
It is recommended to use a PVC plastic tube and oil to calibrate the 4-20mA before inserting into