Page 10
Serial iBootBar v090212d
Serial Operation
Command Line Interface
The Command Line Interface provides complete setup of all function of the iBootBar. Some commands of the CLI require administrative rights. These are
indicated in the table below.
To access the sBB, connect to the serial port and type Enter, the user will be prompted for Username and Password. The default for both is
admin
Outlet Commands
Command
Description
Access
Fact Def
get outlets
Returns the status of ALL the outlets the user has rights to.
User
get outlet <1-8>
Returns the status of the designated outlet. The user must have
rights to the selected outlet.
User
set outlet <1-8> <on/off/cycle>
Sets the selected outlet to the selected state. The user must have
rights to the selected outlet.
User
set outlet <1-8> name <name>
Sets the nam e of the selected outlet of the selected iBootBar. 20
characters max.
Admin
Outlet <#>
get outlet <n> control.on
set outlet <n> control.on <open/closed>
Gets or sets the state that the control input causes the
corresponding outlet to turn On.
Admin
Open
get outlet <1-8> initial.state
set outlet <1-8> initial.state <on/off/last>
Get or set the initial state of the selected outlet of the currently
selected iBootBar. Initial state is the condition of the outlet when the
iBootBar is powered up. This command will be ignored if external
control is enabled with
set external control enable
Admin
Last
Summary of Contents for sBB-2C10