Instruction Manual
SG2 EXTENDED
25
Purpose
Connection
Status
+ 24 Vdc
TEST ON
TEST
Not connected
or 0V
TEST OFF
+ 24 Vdc
RESET ON
RESET
Not connected
or 0V
RESET OFF
+ 24 Vdc
short
(9 m )
SELECT RANGE
Not connected
or 0V
long
(19 m )
EDM
Normally closed
Force-guided relay
contact
+ 24 Vdc
EDM OFF
ENABLE EDM
Not connected
or 0V
EDM ON
OSSD1
AUTO
RESTART
MAN/AUTO RESTART SELECTION
OSSD2
MAN
RESTART
4.1. Notes on connections
For the correct functioning of the SG2 safety light curtains, the following precautions regarding the
electrical connections have to be respected:
Do not place connection cables in contact with or near high-voltage cables and/or cable undergoing
high current variations (e.g. motor power supplies, inverters, etc.);
Do not connect in the same multi-pole cable the OSSD wires of different light curtains;
The TEST wire must be connected through a N.O. button to the supply voltage of the ESPE.
The RESET/RESTART wire must be connected through a N.O. button to the supply voltage of the
ESPE.
The RESET/RESTART button must be located in such a way that the operator can check the
protected area during any test (see chapter 6 “Functioning mode”).
The device is protected internally against overvoltage and overcurrent: the use of other outer parts
is not recommended.