DKG-309 User Manual V-02
(11.05.2009)
- 31 -
Parameter Definition
Unit
Factory
Set
Description
Low Battery Voltage
Warning
V
9.0
If the battery voltage falls below this limit, this will
generate a
LOW BATTERY
warning.
High Battery Voltage
Warning
V
31.0
If the battery voltage goes over this limit, this will
generate a
HIGH BATTERY
warning.
High Battery Voltage
Shutdown
V
33.0
If the battery voltage goes over this limit, this will
generate a
HIGH BATTERY
shutdown
alarm and the
engine will stop.
Mains Waiting Timer
min
0.5
This is the time between the mains voltages entered
within the limits and the generator contactor is
deactivated.
Genset Contactor Timer
sec
1
This is the period after the mains contactor has been
deactivated and before the generator contactor has
been activated.
Mains Contactor Timer
sec
1
This is the period after the generator contactor has
been deactivated and before the mains contactor has
been activated.
Mains Phase Order Enable
-
0
0:
mains phase order checking disabled
1:
if mains phase order is faulty, then a warning is
given and mains contactor deenergized.
Load Shedding Low Limit
KW
0
If the genset power goes below this limit then the
load shedding relay will be deactivated.
Load Shedding High Limit
KW
0
If the genset power goes above this limit then the
load shedding relay will be activated.