Program Group: Controller Configuration (continued)
Exercise Duration
min
10
This parameter defines the exercise duration and
programmed in 10 minute steps up to 24 hours.
Exercise Off/On Load
-
0
0:
Exercise at
TEST
mode
1:
Exercise at
LOAD TEST
mode
Exercise Period
-
1
0:
exercise every day (the exercise will be performed
every day regardless of the day selection of Exercise
Dat and Time parameter).
1:
exercise once per week
2:
exercise once per month (the exercise will be
performed during the first 7 days of each month at the
programmed day and hour).
Remote Start Operation
-
0
0:
NORMAL MODE:
the engine runs when the mains
fail.
1: REMOTE START MODE:
the engine runs when a
signal from the
SPARE-2
input comes, the unit does
not monitor mains voltages.
Simulate Mains Operation
-
0
0:
The
SPARE-2
input has normal function
1:
The
SPARE-2
input simulates mains.
Delayed Simulate Mains
-
0
0:
The
SPARE-2
input has normal function
1:
The
SPARE-2
input has delayed simulate mains
function. See chapter 6.8 for more info.
Modem Enable
-
0
0:
No modem connection, the serial port is connected
to PC
1:
Modem connected.
SMS Enable
-
0
0:
SMS not enabled
1:
SMS enabled
GPRS Call Enable
-
0
0:
standard modem calls
1:
GPRS modem calls
MODBUS Address
-
0
0:
RAINBOW communication protocol.
1-144:
MODBUS communication. This parameter is
also the MODBUS controller address of the unit.
Oil Pressure in psi
-
0
0:
oil pressure display in bars
1:
oil pressure display in psi
Temperature in °F
-
0
0:
temperature display in degrees C
1:
temperature display in degrees F
Flashing Relay Timer
hours
0
Delayed Simulate Mains Operation:
max genset
running time after Simulate Mains signal disappears.
Dual Genset Systems:
flashing relay toggle timer.
Please contact DATAKOM for dual genset mutual
stanby operation.
Real Time Clock Adjust
-
117
This parameter trims precisely the real time clock
circuit.
Values from 0 to 63 speed up the clock with
0.25sec/day steps.
Values from 127 to 64 slow down the clock with
0.25sec/day steps.
Hysteresis Voltage
V
8
This parameter provides the mains and genset voltage
limits with a hysteresis feature in order to prevent
faulty decisions.
For example, when the mains are present, the mains
voltage low limit will be used as the programmed low
limit. When the mains fail, the low limit will be
incremented by this value. It is advised to set this
value to 8 volts.