DKG-309 User Manual
(11.05.2009)
6.12 Date & Time Display
The date & time display is provided for verification.
6.13 Software Version Display
Some additional features are installed within consecutive software releases.
sure of the validity of the status of the unit, the software version needs to be known.
The software version of the unit is displayed together with the data
The software version consists of 2 numbers. The first number
version of the unit.
6.14 Modem Connection
The unit is capable of making modem calls in case of alarm, as well as answering modem
calls made from a remote location.
acceptable.
If the modem is connected
to 1, otherwise faulty operation may occur.
parameters are different from zero, the local PC connection
A maximum of 2 telephone numbers can be defined for outgoing modem calls. In case of
alarm, the unit will attempt to reach control centers associated with each number. In case of modem
connection failure, the call will be repeated up to 30
If SMS message sending is enabled, then only the first telephone number will be
used for modem calls.
Advised modems are DATAKOM types which are powered up from the same DC battery
voltage than the unit. Most of other desktop modems with standard AT commands are also usable, but
it is the user’s responsibility to provide an uninterrupted AC supply source to the modem.
necessary modem cable will be supplied
Modem calls are always terminated by the central RAINBOW software. However the unit does
not allow connection durations exceeding 2 minutes, and hangs up the modem when this period
expires.
The PC program used for remote monitoring and programming is the
software used for RS-232 connection.
Please note that the modem operation is also compatible with the MODBUS communication.
Thus the unit can iniate and receive calls to/from a MODBUS master station. Please review chapter_8
for more details on MODBUS communication.
Date & Time Display
is provided for verification.
Software Version Display
Some additional features are installed within consecutive software releases.
sure of the validity of the status of the unit, the software version needs to be known.
The software version of the unit is displayed together with the data – time information.
The software version consists of 2 numbers. The first number represent the operati
Modem Connection
The unit is capable of making modem calls in case of alarm, as well as answering modem
calls made from a remote location.
GSM
modems and classic cable network (
PSTN
If the modem is connected to the unit, the
Modem Enable
program parameter should be set
to 1, otherwise faulty operation may occur. If
Modem Enable
or
SMS Enable
or
MODBUS Address
parameters are different from zero, the local PC connection will not work.
A maximum of 2 telephone numbers can be defined for outgoing modem calls. In case of
alarm, the unit will attempt to reach control centers associated with each number. In case of modem
connection failure, the call will be repeated up to 30 times with 2 minute intervals.
If SMS message sending is enabled, then only the first telephone number will be
Advised modems are DATAKOM types which are powered up from the same DC battery
ge than the unit. Most of other desktop modems with standard AT commands are also usable, but
it is the user’s responsibility to provide an uninterrupted AC supply source to the modem.
modem cable will be supplied by DATAKOM.
are always terminated by the central RAINBOW software. However the unit does
not allow connection durations exceeding 2 minutes, and hangs up the modem when this period
program used for remote monitoring and programming is the same RAINBO
232 connection.
Please note that the modem operation is also compatible with the MODBUS communication.
Thus the unit can iniate and receive calls to/from a MODBUS master station. Please review chapter_8
communication.
V-02
- 19 -
Some additional features are installed within consecutive software releases. In order to be
sure of the validity of the status of the unit, the software version needs to be known.
time information.
represent the operating software
The unit is capable of making modem calls in case of alarm, as well as answering modem
PSTN
) modems are
program parameter should be set
MODBUS Address
A maximum of 2 telephone numbers can be defined for outgoing modem calls. In case of
alarm, the unit will attempt to reach control centers associated with each number. In case of modem
If SMS message sending is enabled, then only the first telephone number will be
Advised modems are DATAKOM types which are powered up from the same DC battery
ge than the unit. Most of other desktop modems with standard AT commands are also usable, but
it is the user’s responsibility to provide an uninterrupted AC supply source to the modem. The
are always terminated by the central RAINBOW software. However the unit does
not allow connection durations exceeding 2 minutes, and hangs up the modem when this period
same RAINBOW
Please note that the modem operation is also compatible with the MODBUS communication.
Thus the unit can iniate and receive calls to/from a MODBUS master station. Please review chapter_8