V.  Troubleshooting

Symptom

Remedy

Cannot connect to the idap 

card

•  Check network connections such cable and network switch.
•  If private network, check network permission. Contact net

-

work administrator.

•  Perform ping test to check connection.
•  Check the IP address that is assigned and programmed to 

the card. Use a laptop or dap4 display to check this pro

-

grammed IP address. See section II.B and II.C for details.

•  Reboot the card (restart dap4). 
•  Perform Factory reboot and use a laptop to connect directly 

to the card via a cross-over cable to check the card. Again 

see section II.B for details.

System status does not 

show any data or data does 

not update

•  Check the connection to the card. See above
•  Check the dap4 menu setting, menu G- Network Config BMS 

port 1 must be set to BACnet TCP/IP. BMS port 2: N/A

•  Check to make sure dap4 is online.
•  Reboot the card.

Missing data or data does 

not display properly

•  Check the Model and Cooling type setting on Configuration- 

General page

Incorrect Location and unit 

Name

•  Check and correct the location and unit name on Configura

-

tion- General page.

Graph does not display or 

not update

•  Check to make sure logger is enable.
•  Check to make sure sensor is enable.
•  Select update files to this very moment.
•  Reboot the card and wait for few minutes.

No Email on alarms

•  Check to make sure alarms and events are enabling. See 

Configure Email on alarm notification section.

•  Check recipients’ email address, user name, password and 

SMTP server address.

•  Refresh the card.

Card the does respond after 

changing settings

•  Check connection.
•  Perform ping test.
•  Reboot the card

Unit comes back ON  after 

command unit to OFF  mode

•  Check to make sure idap web page is active
•  Check to make sure network connection is okay. Ping test 

can be used to verify connection.

Summary of Contents for idap

Page 1: ......

Page 2: ...Data Aire Inc reserves the right to make design changes for the purpose of product improvement or to withdraw any design without notice...

Page 3: ...ation Unit name Model and Cooling Type 8 B Configure a New IP address If necessary 9 C Configure Email on Alarm Notification 10 D Set Date and Time 11 E Changing User Name and Password 11 IV System Mo...

Page 4: ...ail alarm notifications to allow immediate action as a result of a malfunction Also email logger and graphs Support SNMPv1 v2 BACnet IP and Modbus TCP IP protocols for BMS Building Monitoring System o...

Page 5: ...boot If dap4 is reset the card will go back to the IP address that is programmed on the card 5 The factory default IP address for the idap card is as follows IP address 172 16 0 1 Net Mask 255 255 0 0...

Page 6: ...g the IP under Eth0 IP address Main box and NetMask main box The default setting is DHCP 11 Click Submit after entering the IP address 12 It will take approximately 5 minutes for the IP address change...

Page 7: ...NFIG MEMORIES STATUS 3 Use Select down key i then Enter key to select PCOWEB NET CONFIG the following screen will appear PCOWEB settings PCONET settings 4 Press Enter key to select PCOWEB settings opt...

Page 8: ...nection to the card open a web browser such as Internet Ex plorer Version 10 or newer Mozilla Firefox or Google Chrome to browse the card Click on Go to Administration Area The following screen will a...

Page 9: ...play After entering this information Press F5 on your computer to save and refresh this page your loca tion and unit name will start to appear on your System status page B Configure a New IP address I...

Page 10: ...for sending out emails on alarm are shown above If you do not want a email sent out on a particular alarm merely uncheck clicking on the check mark box the event and send email boxes in the same row...

Page 11: ...r there are fields for user name and pass word Finally enter the recipient s email address and SMTP server address then click on the Store the E mail configuration box Test email notifications Availab...

Page 12: ...n messages whether the corresponding events occur or not 3 Check the email logs Example 1 with no errors Example 2 with error no emails will be sent 4 Restart idap must be reboot when finished monitor...

Page 13: ...time clock synchronization settings will cause time clock and event logging errors To change the date and time go to dap4 menu C Clock and Scheduler To view the clock synchronizer setting click on Dat...

Page 14: ...n 10 or newer Mozilla Firefox or Google Chrome then enter the IP address of the idap card you want to monitor into the web page address box and press Enter If the address is correct the following page...

Page 15: ...Force unit only Equipment runtimes Optional discharge temperature and optional chilled water temperature Discharge temperature and chilled water temperature will not show if an optional discharge tem...

Page 16: ...Log Files To view the return air temperature and humidity graphs for the past 24 hrs click on Data and Graphs menu tab on the left hand of the main system status The following screen will appear Clic...

Page 17: ...o download a log file click on Download all the csv files and graphs or Download the latest csv file in the Data and Graphs section If you select Download the latest csv file only the latest 24 hours...

Page 18: ...in system status page click the Configura tion tab on the left hand side then click General tab and select the View Used Free disk space this message will appear to show the used and free disk space E...

Page 19: ...across the top of the page Consult with factory if software or firmware upgrade are needed G Change Setpoints and Deadbands To modify the system temperature humidity setpoint and deadband simply click...

Page 20: ...be always active during the OFF mode control period and communicate with the idap card In other words idap web page must be active otherwise the system will revert to ON mode if the web page interface...

Page 21: ...21 To turn the system back ON simply click the Change button again then select ON on the Turn System ON OFF window then click Submit...

Page 22: ...IP BMS port 2 N A Check to make sure dap4 is online Reboot the card Missing data or data does not display properly Check the Model and Cooling type setting on Configuration General page Incorrect Loca...

Page 23: ......

Page 24: ......

Reviews: