41 • dap4 User Manual
▼ Press the DOWN key to view the next screen:
The following will be displayed (values are for reference only):
Available Selections:
Firestat Setpoint: The range is 100 to 150°F (factory setting is 150°F)
Hi Temp Alarm:
Yes or No (factory setting is Yes)
Set Point:
The range is 70 to 90°F (factory setting is 80°F)
Lo Temp Alarm:
Yes or No (factory setting is Yes)
Set Point:
The range is 55 to 75°F (factory setting is 60°F)
Note:
If No is selected for the Hi or Lo Temp Alarm, the Set Point will not be displayed.
Once a selection or selections have been made, move the cursor to the title block by pressing the
ENTER key
▼ Press the DOWN key to view the next screen:
The following will be displayed (values are for reference only):
Available Selections:
Lo Disch T Alarm: Yes or No
If Yes is selected, the following will be displayed (value is for reference only):
Return Air Alarms
Firestat Setpoint:
100
o
F
Hi Temp Alarm:
Yes
Set Point:
80
o
F
Lo Temp Alarm:
Yes
Set Point:
60
o
F
Discharge Alarm
Lo Disch T Alarm:
No