103 • dap4 User Manual
dap4 I/O Control Board and Unit Terminal Block Pin ID Number
Control & Alarms – Digital Outputs
I/O Board Pin ID
ID Connector Number
Unit TB
System Blower
NO1
J12-2
TB1-4
Compressor 1
NO2
J12-3
TB1-5
Compressor 2
NO3
J12-4
TB1-6
Opt Cooling 3rd Stage
NO4
J13-2
TB2-37
Opt Cooling 4th Stage
NO5
J13-3
TB2-38
Humidifier
NO6
J13-4
TB1-8
Status Contact
C7
J14-1
TB1-9
NO7
J14-2
TB1-10
Condenser Aux
NO8
J15-1
TB2-47
C8
J15-2
TB2-46
Reheat 1
NO9
J16-2
TB1-7
Reheat 2
NO10
J16-3
TB1-20
Reheat 3
NO11
J16-4
TB1-21
Alarm 3
NO12
J17-1
TB1-45
C12
J17-2
TB1-43
NC-12
J17-3
TB1-44
Alarm 4
NO13
J18-1
TB2-50
C13
J18-2
TB2-48
NO13
J18-3
TB2-49
Alarm 1
NO14
J21-1
TB1-13
C14
J21-2
TB1-11
NC14
J21-3
TB1-12
Alarm 2
NO15
J21-4
TB1-42
C15
J21-5
TB1-40
NC15
J21-6
TB1-41
Opt Energy Saver
NO16
J22-2
TB1-19
Opt Humidifier Drain (Autoflush)
NO17
J22-3
TB2-39
Control – Analog Output
I/O Board Pin ID
ID Connector Number
Unit TB
Water Valve Control
Y1
J4-3
TB2-34
VG0
J4-2
TB2-35
Opt Humidifier Modulating Control
Y2
J4-4
TB2-51
VG0
J4-2
TB2-52
Blower Fan Speed Control
Y3
J4-5
TB4-1, 2
VG0
J4-2
TB4-3,4
SCR Reheat
Y4
J4-6
N/A
VG0
J4-2