4.1.6 Parameters Code Description
Parameters
Code
Default
Precision
Range
Humidity set
(dehumidify)
R01
50%
1%
1%~99%
Air damper automatic
close/open value
R03
50%
1%
1%~99%
Air damper humidity differential
R04
3%
1%
1%~10%
Indoor temp. set
R05
25 (77°F)
0.5 (1°F)
5~35°C (41~95°F)
Humidity set
(humidify)
R06
70%
1%
1%~99%
Humidity differential
(humidify)
R07
3%
1%
1%~10%
Air damper automatic
close/open
H01
1
/
0
- no in use
1
- in use
Filter alarm hour
H02
200
1
0 – no alarm
100 - 990, 1=10 hours
Defrost interval
D01
40 minutes
1 minute
30~60 minutes
Defrost stop
D02
10 minutes
1 minute
1~15 minutes
Defrost start
D03
17 (62°F)
1 (2°F)
1~20°C (34~68°F)
AC fan speed set
F01
1
/
1
– low speed;
2
- medium speed (DC motor
fan: 1,2 - low; 3,4,5 - high);
3
- high speed (DC motor fan:
1,2 - low; 3,4 - medium; 5 -
high)
Fan set under achieved
humidity
F02
1
/
1
- turns off 3 minutes later after
achieved the set humidity;
2
- keeps working after
achieved the set humidity
FAN1, DC fan motor,
speed 1 voltage
F03
500 (5V)
10 (0.1V)
400~950
FAN1, DC fan motor,
speed 2 voltage
F04
600 (6V)
10 (0.1V)
F03~950
FAN1, DC fan motor,
speed 3 voltage
F05
700 (7V)
10 (0.1V)
F04~950
FAN1, DC fan motor,
speed 4 voltage
F06
800 (8V)
10 (0.1V)
F05~950
FAN1, DC fan motor,
speed 5 voltage
F07
900 (9V)
10 (0.1V)
F06~950
FAN2, DC fan motor,
speed 1 voltage
F08
400 (4V)
10 (0.1V)
400~950
FAN2, DC fan motor,
speed 2 voltage
F09
500 (5V)
10 (0.1V)
F08~950
FAN2, DC fan motor,
speed 3 voltage
F10
600 (6V)
10 (0.1V)
F09~950