5. MAINTENANCE
27
•
Keep the unit running, open the inspection door by the receiver and check if there is
enough refrigerant in the receiver and if the sight glass of the refrigerant circuit is free
of bubbles.
If you are in doubt about the condition of the cooling circuit, stop the compressor at once to
avoid damage and call a cooling technician or the Dantherm service.
5.10 Drop catcher
The following steps should be taken to maintain the drop catcher:
•
To get access to the drop catcher, remove the outer cabinet panel and the inner air
guiding plate. Then slide out the drop catcher.
•
Check for dirt and damage. Dirt can be removed by carefully washing the drop catchers.
•
Check the sliding rails for dirt. If necessary, clean them and reinstall the drop catchers.