Jumper Settings
Jumper row A-D: Monitoring Parameters
Position
A: Max Dischg(H)
B: Cutoff (L)
Classic PSALM
C: Idle Per.
D: Tolerance
1
10 l
10 l/h 0%
10 s
1 imp
2
20 l
20 l/h 2/4%
20 s
2 imp
3
50 l
50 l/h 4/8%
50 s
5 imp
4
100 l
100 l/h 6/12%
100 s
10 imp
5
200 l
200 l/h 8/16%
200 s
20 imp
6
500 l
500 l/h 10/20%
500 s
50 imp
7
1000 l
1000 l/h 12/24%
1000 s
100 imp
8
2000 l
2000 l/h 14/28%
2000 s
200 imp
A: Max Dischg:
(H):
No jumper: System uses a default value (200 l), adjustable by PC (hpdis) and
automatically after aminimum 7 day run-in. Otherwise jumper * scale factor.
(L):
Irrespective of jumper settings, a default value (20 l) is used, adjustable by PC (lpdis)
and automatically after a minimum 7 day run-in.
B: Cutoff (Classic):
(H):
Irrespective of jumper settings, a default value (20 l/h) is used, adjustable by PC
(hpcof) and automatically after a minimum 7 day run-in.
(L):
No jumper in row B: Discharge monitor disabled in both phases. Otherwise the
jumper setting is used in Phase L.
PSALM:
the chosen cutoff setting is used in both phases.
No jumper in row C: System uses a default value (1000 sek), adjustable by PC to the
values indicated, and automatically after a minimum 7 day dun-in.
No jumper in row D: seepage monitor disabled.
Jumper row E: Relay Configuration
Pos 1 On/Off = Max.Alarm to J17
Pos 2 On/Off = Seepage Alarm to J17
Pos 3 On/Off = LS-X alarm to J17
Pos 4 On/Off = System errors to J17
Pos 5 On/Off = Pump Stop (valve closed) to J16
Pos 6 On/Off = Holiday to J16
Pos 7 On/Off = Duplicate J17 selected leakage alarms on J16
Pos 8 On/Off = System errors to J16
Jumper row F: Options
Pos 1-3:
Function Selection for digital inputs, se table next page.
Pos 4 On/Off = Liquid Sensor installed/not installed
Pos 5 On/Off = Wet liquid sensor closes/does not close valve
Pos 6 On/Off = IRPT 100 l/imp
Pos 7 On/Off = IRPT 10 l/imp
Pos 8 On/Off = IRPT 1 l/imp